3. In the table that you just selected, find the maximum output current that just exceeds the motor's maximum
current consumption and use the VFD68 Part Number associated with this maximum output current as the
recommended Drive for the motor.
4. Use the same table to determine the recommended cable wiring size for the output current rating.
Table 19: 230 VAC, VFD68Bxx Drives, Maximum Output Amperes and Wiring Sizes
Part
Rated
Number
Capacity,
kW
(HP)
VFD68BBB
0.1 (1/8)
VFD68BCB
0.2 (1/4)
VFD68BDC
0.4 (1/2)
VFD68BFD
0.75 (1)
VFD68BGG
1.5 (2)
VFD68BHG
2.2 (3)
VFD68BJK
3.7 (5)
VFD68BKL
5.5 (7-1/2)
VFD68BLL
7.5 (10)
VFD68BMP
11 (15)
VFD68BNP
15 (20)
1.
The recommended cable wire size is that of the cable (THHW cable) with a continuous maximum permissible
temperature of 75°C (167°F). Assumes that the surrounding air temperature is 40°C (104°F) or less. (Selection
example for use mainly in the United States.)
2.
The recommended cable wire size is that of the cable (PVC cable) with a continuous maximum permissible
temperature of 70°C (158°F). Assumes that the surrounding air temperature is 40°C (104°F) or less. (Selection
example for use mainly in Europe.)
Table 20: 460 VAC, VFD68Cxx Drives, Maximum Output Amperes and Wiring Sizes
Part
Rated
Number
Capacity,
kW
(HP)
VFD68CDF
0.4 (1/2)
VFD68CFF
0.75 (1)
VFD68CGG
1.5 (2)
VFD68CHH
2.2 (3)
VFD68CJJ
3.7 (5)
VFD68CKL
5.5 (7.5)
VFD68CLL
7.5 (10)
VFD68CMP
11 (15)
VFD68CNP
15 (20)
1.
The recommended cable wire size is that of the cable (THHW cable) with a continuous maximum permissible
temperature of 75°C (167°F). Assumes that the surrounding air temperature is 40°C (104°F) or less. (Selection
example for use mainly in the United States.)
2.
The recommended cable wire size is that of the cable (PVC cable) with a continuous maximum permissible
temperature of 70°C (158°F). Assumes that the surrounding air temperature is 40°C (104°F) or less. (Selection
example for use mainly in Europe.)
Maximum
Output
AWG
Current
R/L1, S/L2,
(Amperes)
T/L3
0.8
14
1.4
14
2.5
14
4.2
14
7.0
14
10.0
14
16.5
12
23.8
10
31.8
6
45.0
6
58.0
4
Maximum
Output
AWG
Current
R/L1, S/L2,
(Amperes)
T/L3
1.2
14
2.2
14
3.6
14
5.0
14
8.0
14
12.0
12
16.0
12
23.0
10
29.5
8
VFD68 Variable Frequency Drives
21
Cable Wire Size
1
PVC wires, (mm
U, V, W
R/L1, S/L2,
T/L3
14
2.5
14
2.5
14
2.5
14
2.5
14
2.5
14
2.5
12
4
10
6
8
16
6
16
4
25
Cable Wire Size
1
PVC wires, (mm
U, V, W
R/L1, S/L2,
T/L3
14
2.5
14
2.5
14
2.5
14
2.5
14
2.5
14
4
12
4
10
6
8
10
2
2
)
U, V, W
Earthing
(Ground) cable
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
4
4
6
6
10
6
16
16
25
16
2
2
)
U, V, W
Earthing
(Ground) cable
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
4
4
4
6
10
10
10
Need help?