Date and Time
Daily clock adjustment
Enable Daylight Saving
Enable Auto After Hours
Holidays
Reprogram Holiday Trouble
Sync Enable
19.5.1
Sync Enable
This feature provides a way to synchronize the time on FleX-Net™ once a day. It requires an 8
input adder (DM-1008A) installed on Loop 0. The Type of one of the inputs must be configured
as Sync Input as shown in Figure 104.
Figure 104 8 input adder with the first input configured as Sync Input
When this input is activated, the time on FleX-Net™ is set to the time specified in the Sync
Enable section of the Job Details window. Only the hours and minutes can be set.
The signal must be a momentary dry contact closure of at least 3 seconds duration.
140
The number of seconds (positive or negative) by which
the system adjusts the panel's clock every 24 hours. The
adjustment happens at 01:55 every day.
Enables automatic change to and from daylight saving
time.
Specifies when the system automatically goes into After
Hours mode. If After Hours mode is enabled, then you can
change the detector sensitivity for the times designated as
After Hours (because there will be fewer people in the
facility, the sensitivity might need to be higher).
A list of the defined holidays, when the system will go into
After Hours mode.
Select this check box to put the system into trouble when
there are no future holidays programmed. Specify the
date after which there are no programmed holidays. The
system will be in trouble until more holidays are added, or
until the check box is unselected.
See section 19.5.1.