External electrical connections
FILTER GUARD
PRESENCE DETECTOR
CARBON DIOXIDE SENSOR
WITH RELAY
Operation
An alarm is initiated when the pressure loss exceeds 175 Pa (factory setting 440). The alarm is initiated only if the unit is operating in the
At Home fan speed mode.
Use the Premium panel for enabling the function from the menu Installation and service/Functions/Filter guard.
The filter guard warns that the filter is fouled with a red LED and displays the text: "Change filter" on the Premium control panel.
The code for access to the Installation and service menu is 1234.
Operation
When the presence detector detects occupants in the room, the ventilation unit switches the speed to Boost.
Use the Premium control panel for selecting the function Installation and service/Functions/Boost.
The code for access to the Installation and service menu is 1234.
Operation
If the carbon dioxide content in the air exceeds the limit value, for example to 700 ppm, the ventilation unit will switch to the At Home fan speed.
If the carbon dioxide content in the air exceeds the limit value, for example to 900 ppm, the ventilation unit will switch to the Boost fan speed.
Use the Premium panel for enabling the function from the menu Installation and service/Control/CO
The fan speed in the ventilation unit is determined by the control function that has the highest priority.
If you also want to use the "Away" fan speed, leave it as the normal fan speed in the control panel.
The code for access to the Installation and service menu is 1234.
53
Presence detector
.
2
Boost
At Home
Away