Pedestrian Automatic Closing time is stored (see DIP3 function to enable or
disable the Automatic Closing feature).
7 - Turn DIP1 to Off position
8 - Turn DIP2 to Off position
f
UNCTIONING Of CONTrOL ACCEssOrIEs
ATTENTION: ONLY IMPULsIVE COMMANDs HAVE TO BE CONNECTED.
Make sure that any other type of command accessories (e.g. mass detectors)
used on the installation are set in the IMPULsIVE mode, otherwise, the gate will be
operated even without the protection of the safety devices.
sTEP BY sTEP or AUTOMATIC commands (K BUTT, PED.Button)
DIP5 - ON The K BUTT and PED.Button perform the step by step cyclic
command open-stop-close-open-stop-etc.
DIP5 - Off The K BUTT and PED.Button perform the automatic command:
- the open command, if pressed with the gate completely closed
- the close command, if pressed with the gate completely opened
- no effect, if pressed during the gate opening
- the gate re-open, if pressed while the gate is closing
The K BUTT opens the gate completely, whereas the PED.Button opens the gate
partially as described in Point E.
sTEP BY sTEP or AUTOMATIC commands (radio command)
DIP4 - ON
The RADIO COMMAND perform the step by step cyclic command
open-stop-close-open-stop-etc.
DIP4 - Off The RADIO COMMAND perform the automatic command:
- the open command, if pressed with the gate completely closed
- the close command, if pressed with the gate completely opened
- no effect, if pressed during the gate opening
- the gate re-open, if pressed while the gate is closing
OPEN BUTTON (COM-OPEN)
The button controls the opening movement when the gate is stationary. If activated
while closing, it reopens the gate.
CLOCK fUNCTION
If you want the Clock function must request s1 with firmware 03.
ATTENTION: A CLOCK CONNECTED TO s1 with fw 04 or more ACTIVATEs
THE OPENING MOVEMENT Of THE GATE WITHOUT HAVING THE
PrOTECTION Of THE sAfETY DEVICEs!
The Clock Function permits to keep the gate opened even if, for example, the
Automatic Closing is enabled (DIP3 ON) or somebody commands the gate closing.
It is useful during rush hours, when traffic is heavy and the flow is slow (e.g.
entrance/exit of employees, emergencies in residential areas or car parks and,
temporarily, for removal vans) and it's necessary to keep the gate opened.
CLOCK fUNCTION APPLICATION
It is necessary to request a s1 control panel with firmware 03.
It can be done by connecting a switch and/or a daily/weekly clock either in parallel
to the OPEN button or instead of the OPEN button. When the control board
receives this command, the gate will open and by keeping this contact closed for all
the time of the gate opening, the Clock Function is automatically activated. In fact,
once reached the open position, the gate will remain opened and all of the control
board functions are blocked. Only when OPEN contact is released, the control
board functions are re-activated and the gate will close immediately.
PEDEsTrIAN command (PED.Button - COM)
This command is useful to open the gate partially, just enough, for example, to
permit a pedestrian crossing, see Point E procedure.
From the Pedestrian opening position the Automatic Closing can be enabled
or disabled with DIP3. From the Pedestrian opening position, the gate can be
completely opened by the OPEN or by the K BUTT button or by the RADIO button.
AUTOMATIC CLOsING (from the COMPLETE open position)
The Automatic Closing from the complete open position can be enabled turning
ON the DIP3.
The maximum gap of time that can be programmed is 5 minutes (see Point D).
AUTOMATIC CLOsING (from the PEDEsTrIAN open position)
The Automatic Closing from the pedestrian open position can be enabled turning
ON the DIP3. The maximum gap of time that can be programmed is 5 minutes
(see Point E).
f
UNCTIONING Of sAfETY ACCEssOrIEs
PHOTOCELL (PHOT - COM)
In case the switch DIP6 is in the OFF position, the photocells are active both in
gate opening and in gate closing. In this configuration, if an obstacle cuts the
photocell beam:
- while the gate is closing, the gate will open
- while the gate is opening, the gate will stop and will restart opening when the
obstacle is removed
- while the gate is still, it will not move neither in opening nor in closing
In case of the switch DIP6 is in the ON position, the photocells are active only in
gate closing.
In this configuration, if an obstacle cuts the photocell beam:
- while the gate is closing, the gate will open
- while the gate is opening, the gate will continue open
- while the gate is still, it will open if a open command is request, it will remain
still if a close command is request.
The photocell input (PHOT - COM) is a NORMALLY CLOSED contact.
In case there are more couple of photocells, the contacts from all the photocell
receivers could be connected in series.
In case the photocells are not installed, this contact must be short circuited with a
wire jump (from PHOT to COM) to permit the gate to operate.
AUTOMATIC CLOsING after the transit through the photocell (DIP17 ON)
This option could be useful to close automatically the gate when the vehicle left and
disengaged the photocell beam. If the DIP17 is turned ON, this function is activated
and the PHOTO input will have two purposes:
- detect the obstacle and prevent the gate movement in according with the DIP6
position
- close the gate as soon as the vehicle leaves the photocell beam
If DIP17 ON and DIP6 Off
If the gate is opening and a vehicle crosses the photo beam, the gate will
stop. When the vehicle leaves, the gate will close automatically after 1second
pause.
If DIP17 ON and DIP6 ON
If the gate is opening and a vehicle crosses the photo beam, the gate will
continue to open. When the vehicle leaves, the gate will stop and then closes
automatically after 1second pause.
If the complete gate open position is reached before the vehicle leaving, the DIP17
will be ignored and the automatic closing will be managed in according to the DIP3
position.
PAY ATTENTION: it is highly recommended to check photocells operation at
least every 6 months.
sAfETY sTrIP (EDGE - COM)
If an obstacle presses the safety strip:
- while the gate is still, it will not move neither in opening nor in closing
- while the gate is closing, the gate will open
- while the gate is opening, the gate will close
In case the safety strip is held pressed a further quick reversion, after 2seconds, is
performed. The gate interrupts any movement and this alarm state will be signalled
by the Blinker for 1 minute. The normal gate operations can be restored by pressing
any push button or radio commands.
If after the first safety strip obstacle detection, the safety strip is released and
then engaged again before the end of the gate travelling, the gate interrupts any
movement and this alarm state will be signalled by the Blinker for 1 minute. The
normal gate operations can be restored by pressing any push button or radio
commands.
The safety strip input (EDGE - COM) is a NORMALLY CLOSED contact.
In case there are more than one safety strip, all their contacts could be connected
in series.
In case the safety strip is not installed, this contact must be short circuited
with a wire jump (from EDGE to COM) to permit the gate to operate.
PAY ATTENTION: it is highly recommended to check safety-strips operation
at least every 6 months.
TEsTING THE sAfETY sTrIP equipment (DIP12 ON)
The DIP12 ON enables the Test of safety strip equipment. The Test is performed
every time the gate completes a full opening. It is suitable only if the safety strip
device is equipped with a dedicated power supply input.
In fact, the safety strip equipment power supply input has to be connected to the
A+TEST and A- outputs (DIP12 ON). Automatically, every time the gate completes
a full opening, just before closing, the control board switches OFF the A+TEST and
A- power supply output for a very short time. While the safety strip power supply is
switched OFF, if everything is working fine the safety strip contact (EDGE - COM)
must open. In case the test fails, no other gate manoeuvre will be allowed and the
alarm state will be signalled by the Blinker that will remain on.