4.

TECHNICAL DATA

XWEB is DIN Rail mounting compatible. Snap the orange tabs on the back of the unit to the down position to
f asten. If not using the DIN Rail mounting option, fasten to the mounting surface using the openings in the
mounting tabs.
Dimensions
Weight (without
accessories)
Mounting
Degree of Protection
Enclosure Rating
Power
Overvoltage Category
Rated Impulse Voltage
Type of Action
Pollution Degree
Ambient Operating
Temperature
Shipping and storage
temperature
Relative Humidity
Digital Inputs
Relay Outputs
Digital Output Ratings
RS485 ports
Ethernet ports
USB Ports
MicroSD
Purpose of control
Construction of control
Approvals
1592010930 XWEB1000D PRO STP GB r1.0 25.11.2020.doc
183 x 110 x 59.1 mm
436g
DIN rail mounting device
Indoor use, Open Type (NEMA - UL 50e)
UL 94 V-0
24Vac, 20VA
II
2500V
1.B of N.O.; 1.C of N.C. (Relay 1-4)
2
-40 to 140 °F (-40°C to 65°C)
-40÷85 °C
20-85% RH noncondensing
2, Dry contacts
3
Relay 1 (N.O. & N.C.) 5A, 125/240 VAC, General Purpose, 100K
cycles; 4FLA/4LRA, 250VAC, Motor Load, 100K cycles;
Relay 2 (N.O. & N.C.) 5A, 125/240 VAC, General Purpose, 100K
cycles; 4FLA/4LRA, 250VAC, Motor Load, 100K cycles;
Relay 3 (N.O. & N.C.) 5A, 125/240 VAC, General Purpose, 100K
cycles; 4FLA/4LRA, 250VAC, Motor Load, 100K cycles;
MODBUS Com Ports 1, 2, 3, 4
Ports ETH1, ETH1, ETH0 (ETH1 has no IP)
1
1
Operating control
Incorporated control, intended to be used in Class I or Class II
equipment
CE