19

ELECTRICAL CONNECTIONS

The instrument is provided with:
2 removable terminal blocks MOLEX MICROFIT 18 and 10 ways for power supply voltage / digital and
analogue inputs and modulating outputs
1 removable terminal blocks STELVIO 6 ways for the remote keyboard connections, RS485 and LAN
1 removable terminal blocks AMP 10 ways for the relay outputs
5 ways connector for TTL RS485 interface outputs
Wiring cables:
DWDE15-KIT
DWDE30-KIT
Wire size:
• signal cable AWG 24
• power supply cable AWG 22
General notes:
Check the connecitons and the line voltage before turning on the power supply.
Keep low voltage cables, such as analogue/digital inputs/outputs and probes, away from power cables
and terminals.
Respect the maximum load current of each relay output.
Some contactors can produce very high electrical stresses on the relay contacts mounted in the device.
Dixell suggests to carefully check the technical documentation of the contactors and follow the instructions
contained in this doumentation (commercial documentation is not a reference for theese information). To
protect the relay contacts of the device, verify the need to use electrical disturbance suppressors or excess
voltage protections.
20

TECHNICAL DATA

20.1 ELECTRICAL SPECIFICATIONS

Housing:
Colour:
Dimensions:
Mounting device:
Degree of protection:
Power Supply:
Rated power:
Rated Impulse Voltage:
Overvoltage category:
Comparative Tracking Index (CTI):
Type of action:
1592022020 iCHILL 100D EVO QRG EN rel. 2.0 23.02.2022
1.5mt
3.0mt
Self-estinguishing PC-ABS Thermoplastic
RAL7012
4 DIN Rail
On a DIN rail (EN 50022, DIN 43880)
IP10 - Indoor use, Open Type
12Vac/dc
24Vac/dc
Max. 10VA
4000V
II
300V
1B
-10% ÷ 15%, 50/60Hz, or
-10% ÷ 10%, 50/60Hz
38/40