Repairs
(cont.)
Check the temperature limiter
Checking and replacing pressure differential sensor
Check the sensor in case of fault messages concerning the differential pressure
sensor:
&
correct installation
&
electrical connection
&
correct position of the O-rings inside the adaptor
&
are the test nipples closed with plugs?
Replace the sensor if fault messages persist.
If the burner control unit cannot be
reset after a fault shutdown, although
the boiler water temperature is below
approx. 75 °C:
&
Pull the leads from temperature lim-
iter A.
&
Check the continuity of the tempera-
ture limiter with a multimeter.
&
Remove faulty temperature limiter.
&
Install a new temperature limiter.
&
After commissioning, press reset
button E on the control unit.