Viessmann Vitodens 333 Service Instructions Manual page 79

Compact gas fired condensing boiler natural gas and lpg version
Hide thumbs Also See for Vitodens 333:
Table of Contents

Advertisement

Checking and acknowledging faults
Display
Const.
fault code
C7
X
Cd
X
CE
X
CF
dA
db
dd
dE
E4
X
Weat-
System
h.
character-
comp.
istics
X
Control
mode,
max. pump
speed
X
Control
mode
X
Control
mode
X
Control
mode
X
Control
mode with-
out room
influence
X
X
X
X
Burner
blocked
Troubleshooting
(cont.)
Cause
Remedy
Communication
Check coding
fault – variable
address E5
speed heating cir-
settings;
cuit pump, heating
check heating
circuit A1
circuit pump
DIP switch
settings
Communication
Check Vito-
error Vitocom 100
com 100 and
(KM BUS)
connections
Communication
Check con-
fault – ext. exten-
nections and
sion
coding ad-
dress 2E set-
ting
Communication
Replace LON
fault – LON com-
communica-
munication module
tion module
Heating circuit A1
Check room
room temperature
temperature
sensor –
sensor shorted out
heating cir-
cuit A1
Heating circuit M2
Check room
room temperature
temperature
sensor –
sensor shorted out
heating cir-
cuit M2
Heating circuit A1
Check room
room temperature
temperature
sensor –
sensor lead break
heating cir-
cuit A1
Heating circuit M2
Check room
room temperature
temperature
sensor –
sensor lead break
heating cir-
cuit M2
Fault – supply vol-
Replace con-
tage
trol unit
79