Viessmann Vitodens 333 Service Instructions Manual page 47

Compact gas fired condensing boiler natural gas and lpg version
Hide thumbs Also See for Vitodens 333:
Table of Contents

Advertisement

Code 2
(cont.)
Coding
Internal
circulation
pump
21
ON
22
ON
23
ON
Coding in
Function mode
the as de-
livered
condition
Address:
value
Boiler/burner
52:0
Without flow tempera-
ture sensor for low loss
header
54:0
Without solar control
unit
Domestic hot water
56:0
DHW temperature ad-
justable from 10 to max.
60 °C
58:0
Without auxiliary func-
tion for DHW loading
Heating cir-
Heating cir-
cuit pump
cuit pump
Heating cir-
Heating cir-
cuit without
cuit with
mixer
mixer
OFF
Control funct. OFF
OFF
OFF
OFF
OFF
Coding
change
Address:
value
52:1
54:1
54:2
56:1
58:10
to
58:60
Coding
Cylinder loading pump
Control funct.
OFF
Possible change
With flow temperature
sensor for low loss head-
er (automatic adjustment
upon recognition)
With Vitosolic 100 (auto-
matic adjustment on re-
cognition)
With Vitosolic 200 (auto-
matic adjustment on re-
cognition)
DHW temperature adjus-
table from 10 to above
60 °C (subject to boiler
coding card)
Observe the max. per-
missible DHW tempera-
ture
Input of a 2nd set DHW
value; adjustable from 10
to 60 °C
47