Checking and acknowledging faults
Display
Const.
fault code
F3
X
F4
X
F7
X
F8
X
F9
X
Weat-
System
h.
character-
comp.
istics
X
Burner in
fault state
X
Burner in
fault state
X
Burner
blocked
X
Burner in
fault state
X
Burner in
fault state
Troubleshooting
(cont.)
Cause
Remedy
Flame signal is al-
Check ionisa-
ready present at
tion electrode
burner start
and leads.
Press E.
No flame signal is
Check ionisa-
present
tion electrode
and leads,
measure ioni-
sation cur-
rent, check
gas pressure,
check gas
combination
valve, igni-
tion, ignition
module, igni-
tion electro-
des and
condensate
drain.
Press E.
Differential pres-
Check differ-
sure sensor faulty
ential pres-
sure sensor
and lead.
Fuel valve closes
Check gas
too late
combination
valve. Check
both control
paths.
Press E.
Fan speed too low
Check fan,
at burner start
check fan
cables and
supply, check
fan control.
Press E.