Coding
Code 2
(cont.)
Coding in
Function mode
the as de-
livered
condition
Address:
value
25:0
*
1
No recognition of out-
side temperature sen-
sor or fault monitoring
(only in i)
28:0
No burner interval igni-
tion
2E:0
Without external exten-
sion
2F:0
Venting program/filling
program inactive
30:1
Internal variable speed
circulation pump (auto-
matic adjustment)
31:65
Set speed of the inter-
nal circulation pump
when operated as boiler
circuit pump 65 %, de-
faulted by the boiler
coding card
32:0
Signal "External lock-
out" on circulation
pumps: All pumps are
controlled
Coding
Internal
circula-
tion pump
0
Control
funct.
1
Control
funct.
*1
Only for constant temperature control units.
44
Coding
change
Address:
value
25:1
28:1
2E:1
2F:1
2F:2
30:0
31:0
to
31:100
32:1
to
32:15
Heating cir-
Heating circuit
cuit pump
pump
Heating cir-
Heating circuit
cuit without
with mixer
mixer
Control funct. Control funct.
Control funct. Control funct.
Possible change
Recognition of outside
temperature sensor and
fault monitoring
The burner is forced ON
once every 24 hours
With external extension
(automatic adjustment on
connection)
Venting program active
Filling program active
Internal circulation pump
without variable speed
(e.g. temporarily for ser-
vice)
Set speed adjustable
from 0 to 100 %
Signal "External lockout"
on circulation pumps:
See the following table
Cylinder loading
pump
Control funct.
OFF