Repairs
(cont.)
Checking the flue gas temperature sensor
The flue gas temperature sensor locks out the boiler when the permissible flue
gas temperature is exceeded. Reset the interlock after the flue gas system has
cooled down, by pressing reset button E.
1. Pull the leads off flue gas tempera-
ture sensor A.
2. Check the sensor resistance and
compare actual values with the
curve.
3. Replace the sensor in case of
severe deviation.
Troubleshooting
87