Viessmann Vitodens 333 Service Instructions Manual page 41

Compact gas fired condensing boiler natural gas and lpg version
Hide thumbs Also See for Vitodens 333:
Table of Contents

Advertisement

Code 1
(cont.)
Coding in
Function mode
the as de-
livered
condition
Address:
value
Level A1
d4:0
*
1
Heating curve level =
0
Codes
Coding in
Function mode
the as de-
livered
condition
Address:
value
Summer econ. M2
A5:5
*
1
With heating circuit
pump logic function
Min. flow temp. M2
C5:20
Electronic minimum
flow temperature limit:
20 °C
Max. flow. temp. M2
C6:75
*
1
Electronic maximum
flow temperature limit at
75 °C
Slope M2
d3:14
*
1
Heating curve slope =
1.4
Level M2
d4:0
*
1
Heating curve level =
0
*1
Only for weather-compensated control units.
Coding
Possible change
change
Address:
value
d4:–13
Heating curve level ad-
justable from –13 to 40
to
d4:40
(see page 34)
Coding
Possible change
change
Address:
value
A5:0
Without heating circuit
pump logic function
C5:1
Minimum limit adjustable
to
from 1 to 127 °C
C5:127
C6:10
Maximum limit adjustable
to
from 10 to 127 °C
C6:127
d3:2
Heating curve slope ad-
to
justable from 0.2 to 3.5
d3:35
(see page 34)
d4:–13
Heating curve level ad-
justable from –13 to 40
to
d4:40
(see page 34)
Coding
41

Advertisement