Viessmann Vitodens 333 Service Instructions Manual page 75

Compact gas fired condensing boiler natural gas and lpg version
Hide thumbs Also See for Vitodens 333:
Table of Contents

Advertisement

Checking and acknowledging faults
Constant temperature control unit
Display
Const.
fault code
0F
X
10
X
18
X
20
X
28
X
Note
The fault can be acknowledged
with d. The fault message in the dis-
play will be hidden, but red fault indi-
cator U continues to flash. A new fault
message will be displayed if an
acknowledged fault is not removed by
the following morning.
Calling up acknowledged fault mes-
sages
Press d for approx. 2 s; select the
acknowledged fault with a or b.
Weat-
System
h.
character-
comp.
istics
X
Control
mode
X
Controls
according
to 0 °C out-
side tem-
perature
X
X
Controls
without
flow tem-
perature
sensor
(low loss
header)
X
Troubleshooting
(cont.)
Cause
Remedy
Maintenance
Carry out
maintenance.
Set code 24:0
after mainte-
nance
Outside tempera-
Check out-
ture sensor shorted
side tempera-
out
ture sensor
(see page 83)
Outside tempera-
ture sensor lead
break
System flow tem-
Check low
perature sensor
loss header
shorted out
sensor (see
page 84)
System flow tem-
perature sensor
lead break
75