Initial start-up, inspection, maintenance
Further details regarding the individual steps
Venting the boiler
Venting the heating system
1. Close the gas shut-off valve and
start the control unit.
8
(cont.)
1. Close the shut-off valves on the
heating water side.
2. Connect the drain hose on valve A
with a drain outlet.
3. Open valve A and fill valve in the
heating return, and vent at mains
pressure, until no sound of escap-
ing air can be heard anymore.
4. Close valve A and fill valve in the
heating return, and open the pri-
mary shut-off valves.
2. Activate the venting program via
coding address 2F:1.
Note
To call up code 1 and for setting the
coding address, see page 39.
For function and sequence of the
venting program, see page 103.
Whilst venting is in progress, the
display shows "EL" (constant tem-
perature control unit) or "Venting"
(weather-compensated control
unit).
3. Check the system pressure.