Troubleshooting
Checking and acknowledging faults
Display
Const.
fault code
E5
X
E6
X
F0
X
F1
X
F2
X
80
Weat-
System
h.
character-
comp.
istics
X
Burner
blocked
X
Burner in
fault state
X
Burner
blocked
X
Burner in
fault state
X
Burner in
fault state
(cont.)
Cause
Remedy
Internal fault
Check ionisa-
tion electrode
and leads.
Check flue
gas system
for sound-
ness.
Press E.
Flue gas/air supply
Check flue
system blocked
gas/air supply
system.
Check differ-
ential pres-
sure sensor.
Press E.
Internal fault
Replace con-
trol unit
Flue gas tempera-
Check heat-
ture limiter has re-
ing system
sponded
water level.
Vent heating
system.
Press reset
button E
after flue gas
system has
cooled down.
Temperature limiter
Check heat-
has responded
ing system
water level.
Check circu-
lation pump.
Vent heating
system.
Check tem-
perature limit-
er and leads.
Press E.