ClimateMaster Tranquility 30 Digital TE Series Installation, Operation & Maintenance Instructions Manual

ClimateMaster Tranquility 30 Digital TE Series Installation, Operation & Maintenance Instructions Manual

Residential horizontal, vertical & downflow packaged geothermal heat pumps
Hide thumbs Also See for Tranquility 30 Digital TE Series:

Advertisement

Quick Links

Advertisement

Table of Contents
loading

Summary of Contents for ClimateMaster Tranquility 30 Digital TE Series

  • Page 1: Table Of Contents

    Tranquility 30 Digital ® (TE) Series IOM 97B0045N04 Residential Horizontal, Vertical & Downflow Packaged Geothermal Heat Pumps Installation, Operation & Maintenance Instructions Rev.: October 5, 2021 Table of Contents Model Nomenclature Electrical—Thermostat Wiring Storage Wiring Diagrams 35–36 Pre-Installation ECM Blower Control Vertical Installation Blower Data Horizontal Installation...
  • Page 2 Tranquility 30 Digital ( TE) Series IOM - 60Hz HFC-410A ® R e v . : O c t o b e r 5 , 2 0 2 1 This page was intentionally left blank. G e o t h e r m a l H e a t i n g a n d C o o l i n g...
  • Page 3: Model Nomenclature

    Tranquility 30 Digital ( TE) Series IOM - 60Hz HFC-410A ® R e v . : O c t o b e r 5 , 2 0 2 1 Model Nomenclature: General Overview 4 5 6 0 2 6 0 2 C L T STANDARD SERIES S = Standard...
  • Page 4 Tranquility 30 Digital ( TE) Series IOM - 60Hz HFC-410A ® R e v . : O c t o b e r 5 , 2 0 2 1 General Information Safety Warnings, cautions and notices appear throughout this CAUTION: Indicates a potentially hazardous situation or an manual.
  • Page 5: Storage

    Tranquility 30 Digital ( TE) Series IOM - 60Hz HFC-410A ® R e v . : O c t o b e r 5 , 2 0 2 1 General Information ⚠ ⚠ Inspection CAUTION! Upon receipt of the equipment, carefully check the shipment against the bill of lading.
  • Page 6: Vertical Installation

    Power Supply Tranquility 30 Digital ( TE) Series IOM - 60Hz HFC-410A 3 / 4" [19.1mm] ® HV Knockout [41.3 mm] [40.5 mm] 1 / 2" [12.7mm] R e v . : O c t o b e r 5 , 2 0 2 1 Knockout Low Voltage 1.18 [30.0 mm]...
  • Page 7 Tranquility 30 Digital ( TE) Series IOM - 60Hz HFC-410A ® R e v . : O c t o b e r 5 , 2 0 2 1 Horizontal Installation Horizontal Unit Location Mounting Horizontal Units Packaged units are not designed for outdoor installation. Horizontal units have 4 hanger brackets partially attached at Locate the unit in an INDOOR area that allows enough space the factory, one at each corner.
  • Page 8: Horizontal Installation

    Tranquility 30 Digital ( TE) Series IOM - 60Hz HFC-410A ® R e v . : O c t o b e r 5 , 2 0 2 1 Horizontal Installation Figure 5: Horizontal Unit Pitch Front 2’ [61cm] Service Access 2’...
  • Page 9 Tranquility 30 Digital ( TE) Series IOM - 60Hz HFC-410A ® R e v . : O c t o b e r 5 , 2 0 2 1 Horizontal Installation Field Conversion of Air Discharge Figure 7: Left Return Side to Back Overview - Horizontal units can be field converted Remove Screws Water...
  • Page 10: Condensate And Water Connection

    Tranquility 30 Digital ( TE) Series IOM - 60Hz HFC-410A ® R e v . : O c t o b e r 5 , 2 0 2 1 Condensate and Water Connection Condensate Piping Water Connections Pitch the unit toward the drain as shown in Figure 5 to Swivel piping fittings are used for water connections that improve the condensate drainage.
  • Page 11: Vflow ™ Heat Pump

    Tranquility 30 Digital ( TE) Series IOM - 60Hz HFC-410A ® R e v . : O c t o b e r 5 , 2 0 2 1 vFlow Heat Pump Applications Overview ® Figure 11a: Typical Closed-Loop Application (with vFlow is a revolutionary new, intelligent, and efficient way to ®...
  • Page 12: Closed Loop Heat Pump Applications

    Tranquility 30 Digital ( TE) Series IOM - 60Hz HFC-410A ® R e v . : O c t o b e r 5 , 2 0 2 1 Closed Loop Heat Pump Applications with Internal Flow Controller Figure 12: Internal Flow Controller Units with internal flow control come with a built-in variable speed pump, an expansion tank, flushing ports and three- way valves (used to flush the unit).
  • Page 13 Tranquility 30 Digital ( TE) Series IOM - 60Hz HFC-410A ® R e v . : O c t o b e r 5 , 2 0 2 1 Closed Loop Heat Pump Applications with Internal Flow Controller Figure 13: Standard Head Variable Pump Performance No Check Valve With Check...
  • Page 14: Flushing The Earth Loop

    Tranquility 30 Digital ( TE) Series IOM - 60Hz HFC-410A ® R e v . : O c t o b e r 5 , 2 0 2 1 Flushing the Earth Loop ⚠ ⚠ Once piping is completed between the unit and the ground WARNING! loop, final purging and charging of the loop is needed.
  • Page 15 Tranquility 30 Digital ( TE) Series IOM - 60Hz HFC-410A ® R e v . : O c t o b e r 5 , 2 0 2 1 Flushing the Earth Loop Figure 15b: Valve Position B - Unit Fill / Flush NOTICE: Actual flushing time require will vary for each installation due to piping length, configuration, and flush cart pump capacity.
  • Page 16 Tranquility 30 Digital ( TE) Series IOM - 60Hz HFC-410A ® R e v . : O c t o b e r 5 , 2 0 2 1 Flushing the Earth Loop Loop static pressure will fluctuate with the seasons and NOTICE: It is recommended to run the unit in the cooling, pressures will be higher in the winter months than during then heating mode for 15-20 minutes each to ‘temper’...
  • Page 17: Multiple Unit Piping And Flushing

    Tranquility 30 Digital ( TE) Series IOM - 60Hz HFC-410A ® R e v . : O c t o b e r 5 , 2 0 2 1 Multiple Unit Piping and Flushing Table 2: Internal 3-Way Flushing Valve Data Often projects require more than one heat pump.
  • Page 18 Tranquility 30 Digital ( TE) Series IOM - 60Hz HFC-410A ® R e v . : O c t o b e r 5 , 2 0 2 1 Multiple Unit Piping and Flushing Multiple Units with Internal Flow Controllers The simplest multiple unit system is one with two (or more) units utilizing internal Flow Controllers with no external pumps or flushing valves.
  • Page 19 Tranquility 30 Digital ( TE) Series IOM - 60Hz HFC-410A ® R e v . : O c t o b e r 5 , 2 0 2 1 Multiple Unit Piping and Flushing Multiple Units with Internal Flow Controllers and Common Flushing Ports Figure 16b: Multiple Units with Internal Flow Controllers and External Flushing Valves Ground Loop Size for Heat Pump...
  • Page 20: Ground Loop Heat Pump Applications

    R e v . : O c t o b e r 5 , 2 0 2 1 Ground Loop Heat Pump Applications Antifreeze Selection - General Contact your ClimateMaster distributor if you have any In areas where minimum entering loop temperatures drop questions as to antifreeze selection.
  • Page 21: Low Temperature Cutout Selection

    Tranquility 30 Digital ( TE) Series IOM - 60Hz HFC-410A ® R e v . : O c t o b e r 5 , 2 0 2 1 Ground Loop Heat Pump Applications Chart 1a: Methanol Specific Gravity about 10 gallons [37.9 liters] total. If more than one tankful is required, the tank should be drained immediately 1.000 by opening the waste valve of the flush cart noting the...
  • Page 22: Closed Loop-External Central

    Tranquility 30 Digital ( TE) Series IOM - 60Hz HFC-410A ® R e v . : O c t o b e r 5 , 2 0 2 1 Closed Loop - External Central Pumping Applications Figure 18: Typical Closed Loop with Central Pumping Application (with Internal Modulating Motorized Valve Shown) To Thermostat Internal Motorized Modulating Valve...
  • Page 23: Open Loop Or Ground-Water

    Tranquility 30 Digital ( TE) Series IOM - 60Hz HFC-410A ® R e v . : O c t o b e r 5 , 2 0 2 1 Open Loop or Ground-Water Heat Pump Applications Figure 20: Typical Open Loop/Well Application Open Loop - Ground Water Systems Typical open loop piping is shown in Figure 20.
  • Page 24 Tranquility 30 Digital ( TE) Series IOM - 60Hz HFC-410A ® R e v . : O c t o b e r 5 , 2 0 2 1 Open Loop or Ground-Water Heat Pump Applications Pressure Tank and Pump Water Coil Low Temperature Limit Setting Use a closed, bladder-type pressure tank to minimize For all open loop systems the 30°F [-1.1°C] LT1 setting...
  • Page 25: Water Quality Requirements

    All closed water loop systems should undergo water quality testing and be maintained to the water quality standards listed in this table. CLIMATEMASTER WATER QUALITY STANDARDS For Closed-Loop and Open-Loop Systems Heat Exchanger Type...
  • Page 26 ® R e v . : O c t o b e r 5 , 2 0 2 1 Water Quality Requirements 1. The ClimateMaster Water Quality Table provides Hydrogen Sulfide has an odor of rotten eggs. If α water quality requirements for coaxial & brazed one detects this smell, a test for H2S must be plate heat exchangers.
  • Page 27 Tranquility 30 Digital ( TE) Series IOM - 60Hz HFC-410A ® R e v . : O c t o b e r 5 , 2 0 2 1 Water Quality Requirements Measuring Earth Ground Resistance 0.02 Well Casing Building Ground Rod OHM meter Measure the earth ground bond using an Ohm meter between the building's ground rod and the steel well casing.
  • Page 28 Tranquility 30 Digital ( TE) Series IOM - 60Hz HFC-410A ® R e v . : O c t o b e r 5 , 2 0 2 1 Water Quality Requirements Measuring Electrolysis Voltage and Current 300mV Heat Pump Volt Meter Wire Electrode inserted into port for Voltage measurement...
  • Page 29: Hot Water Generator

    Tranquility 30 Digital ( TE) Series IOM - 60Hz HFC-410A ® R e v . : O c t o b e r 5 , 2 0 2 1 Hot Water Generator The HWG (Hot Water Generator) or desuperheater option It is always advisable to use water softening equipment on provides considerable operating cost savings by utilizing domestic water systems to reduce the scaling potential and...
  • Page 30 Tranquility 30 Digital ( TE) Series IOM - 60Hz HFC-410A ® R e v . : O c t o b e r 5 , 2 0 2 1 Hot Water Generator Installation Figure 23: Anti-Scald Valve Piping Connections ANTI-SCALD The HWG is controlled by two sensors and the DXM2 micro- COLD WATER VALVE PIPING...
  • Page 31 Tranquility 30 Digital ( TE) Series IOM - 60Hz HFC-410A ® R e v . : O c t o b e r 5 , 2 0 2 1 Hot Water Generator ⚠ ⚠ 4. Inspect all work for leaks. WARNING! 5.
  • Page 32: Electrical-Line Voltage

    Tranquility 30 Digital ( TE) Series IOM - 60Hz HFC-410A ® R e v . : O c t o b e r 5 , 2 0 2 1 Electrical - Line Voltage ⚠ ⚠ Electrical - Line Voltage WARNING! All field installed wiring, including electrical ground, must comply with the National Electrical Code as well as all WARNING! To avoid possible injury or death due to...
  • Page 33: Electrical-Low Voltage Wiring

    Tranquility 30 Digital ( TE) Series IOM - 60Hz HFC-410A ® R e v . : O c t o b e r 5 , 2 0 2 1 Electrical - Low Voltage Wiring Figure 26: Tranquility Low Voltage Field Wiring Table 9: Accessory Relay 2 Configuration DIP 2.4 DIP 2.5...
  • Page 34: Electrical-Thermostat Wiring

    ⚠ Compressor Compressor Stage 2 CAUTION! Auxiliary Heat Dehumidification CAUTION! Refrigerant pressure activated water regulating Reversing Valve valves should never be used with ClimateMaster equipment. ⚠ ⚠ 24Vac Hot CAUTION! 24Vac Common Fault LED CAUTION! If communicating thermostat is not installed, a...
  • Page 35: Wiring Diagrams

    Tranquility 30 Digital ( TE) Series IOM - 60Hz HFC-410A ® R e v . : O c t o b e r 5 , 2 0 2 1 DXM2 Wiring Diagram with Internal Flow Controller - 96B0005N60 This diagram includes typical wiring details but is not applicable to all units. For specific unit wiring, refer to the diagram or the units’...
  • Page 36 Tranquility 30 Digital ( TE) Series IOM - 60Hz HFC-410A ® R e v . : O c t o b e r 5 , 2 0 2 1 DXM2 Wiring Diagram with Motorized Modulating Water Valve - 96B0005N62 This diagram includes typical wiring details but is not applicable to all units. For specific unit wiring, refer to the diagram or the units’...
  • Page 37: Ecm Blower Control

    Tranquility 30 Digital ( TE) Series IOM - 60Hz HFC-410A ® R e v . : O c t o b e r 5 , 2 0 2 1 ECM Blower Control The ECM fan is controlled directly by the DXM2 control board Special Note for AHRI Testing: To achieve rated airflow for that converts thermostat inputs and CFM settings to signals AHRI testing purposes, it is necessary to change the CFM...
  • Page 38: Blower Data

    Tranquility 30 Digital ( TE) Series IOM - 60Hz HFC-410A ® R e v . : O c t o b e r 5 , 2 0 2 1 ECM Blower Performance Data Table 10: Tranquility 30 (TE) Series ECM Blower Performance Data Table ®...
  • Page 39: Dxm2 Controls

    Tranquility 30 Digital ( TE) Series IOM - 60Hz HFC-410A ® R e v . : O c t o b e r 5 , 2 0 2 1 DXM2 Controls DXM2 iGate Controller DXM2 is the next generation in DIP Switches –...
  • Page 40: Dxm2 Layout And Connection

    N.C. N.O. N.O. Fan Enable Fan Speed Tranquility 30 Digital ( TE) Series IOM - 60Hz HFC-410A ® R e v . : O c t o b e r 5 , 2 0 2 1 Test DXM2 Layout and Connections Micro Alarm Relay...
  • Page 41: Unit Commissioning And Operating Conditions

    Tranquility 30 Digital ( TE) Series IOM - 60Hz HFC-410A ® R e v . : O c t o b e r 5 , 2 0 2 1 Unit Commissioning And Operating Conditions Operating Limits Environment – Units are designed for indoor installation only. Never install units in areas subject to freezing or where humidity levels could cause cabinet condensation (such as unconditioned spaces subject to 100% outside air).
  • Page 42: Unit Start-Up And Operating Conditions

    Tranquility 30 Digital ( TE) Series IOM - 60Hz HFC-410A ® R e v . : O c t o b e r 5 , 2 0 2 1 Unit Start-Up and Operating Conditions ⚠ ⚠ Unit and System Checkout CAUTION! BEFORE POWERING SYSTEM, please check the following: CAUTION! Verify that ALL water valves are open and...
  • Page 43: Unit Start-Up Procedure

    Tranquility 30 Digital ( TE) Series IOM - 60Hz HFC-410A ® R e v . : O c t o b e r 5 , 2 0 2 1 Unit Start-Up Procedure a. Go into Manual Mode activate Y1, and Y2 for Heating. SERVICE MODE Also manually increase CFM until desired heating MANUAL OPERATION...
  • Page 44: Unit Operating Conditions

    Tranquility 30 Digital ( TE) Series IOM - 60Hz HFC-410A ® R e v . : O c t o b e r 5 , 2 0 2 1 Unit Start-Up Procedure If performance during any mode appears abnormal, refer to the DXM2 section or troubleshooting section of this manual.
  • Page 45 Tranquility 30 Digital ( TE) Series IOM - 60Hz HFC-410A ® R e v . : O c t o b e r 5 , 2 0 2 1 Unit Operating Conditions - TE Table 15: TE Series Typical Unit Operating Pressures and Temperatures TE026 Full Load Cooling - without HWG active Full Load Heating - without HWG active...
  • Page 46 Tranquility 30 Digital ( TE) Series IOM - 60Hz HFC-410A ® R e v . : O c t o b e r 5 , 2 0 2 1 Unit Operating Conditions - TE Table 15: TE Series Typical Unit Operating Pressures and Temperatures: Continued TE064 Full Load Cooling - without HWG active Full Load Heating - without HWG active...
  • Page 47: Performance Data

    Tranquility 30 Digital ( TE) Series IOM - 60Hz HFC-410A ® R e v . : O c t o b e r 5 , 2 0 2 1 Performance Data — Tranquility 30 Digital - Model 026 ® Part Load - with vFlow ®...
  • Page 48 Tranquility 30 Digital ( TE) Series IOM - 60Hz HFC-410A ® R e v . : O c t o b e r 5 , 2 0 2 1 Performance Data — Tranquility 30 Digital - Model 026 ® Full Load - with vFlow ®...
  • Page 49 Tranquility 30 Digital ( TE) Series IOM - 60Hz HFC-410A ® R e v . : O c t o b e r 5 , 2 0 2 1 Performance Data — Tranquility 30 Digital - Model - 038 ® Part Load - with vFlow ®...
  • Page 50 Tranquility 30 Digital ( TE) Series IOM - 60Hz HFC-410A ® R e v . : O c t o b e r 5 , 2 0 2 1 Performance Data — Tranquility 30 Digital - Model - 038 ® Full Load - with vFlow ®...
  • Page 51 Tranquility 30 Digital ( TE) Series IOM - 60Hz HFC-410A ® R e v . : O c t o b e r 5 , 2 0 2 1 Performance Data — Tranquility 30 Digital - Model - 049 ® Part Load - with vFlow ®...
  • Page 52 Tranquility 30 Digital ( TE) Series IOM - 60Hz HFC-410A ® R e v . : O c t o b e r 5 , 2 0 2 1 Performance Data — Tranquility 30 Digital - Model - 049 ® Full Load - with vFlow ®...
  • Page 53 Tranquility 30 Digital ( TE) Series IOM - 60Hz HFC-410A ® R e v . : O c t o b e r 5 , 2 0 2 1 Performance Data — Tranquility 30 Digital - Model - 064 ® Part Load - with vFlow ®...
  • Page 54 Tranquility 30 Digital ( TE) Series IOM - 60Hz HFC-410A ® R e v . : O c t o b e r 5 , 2 0 2 1 Performance Data — Tranquility 30 Digital - Model - 064 ® Full Load - with vFlow ®...
  • Page 55 Tranquility 30 Digital ( TE) Series IOM - 60Hz HFC-410A ® R e v . : O c t o b e r 5 , 2 0 2 1 Performance Data — Tranquility 30 Digital - Model - 072 ® Part Load - with vFlow ®...
  • Page 56 Tranquility 30 Digital ( TE) Series IOM - 60Hz HFC-410A ® R e v . : O c t o b e r 5 , 2 0 2 1 Performance Data — Tranquility 30 Digital - Model - 072 ® Full Load - with vFlow ®...
  • Page 57: Preventive Maintenance

    Tranquility 30 Digital ( TE) Series IOM - 60Hz HFC-410A ® R e v . : O c t o b e r 5 , 2 0 2 1 Preventive Maintenance Water Coil Maintenance Condensate Drain (Direct ground water applications only) - If the system is In areas where airborne bacteria may produce a “slimy”...
  • Page 58: Troubleshooting

    Tranquility 30 Digital ( TE) Series IOM - 60Hz HFC-410A ® R e v . : O c t o b e r 5 , 2 0 2 1 Troubleshooting General Table 17: Nominal resistance at various temperatures If operational difficulties are encountered, perform Resistance Resistance Temp (ºC)
  • Page 59 Tranquility 30 Digital ( TE) Series IOM - 60Hz HFC-410A ® R e v . : O c t o b e r 5 , 2 0 2 1 Troubleshooting Outputs Fault Temp Conditions – This option displays the DXM2 The compressor and reversing valve relays are 24VAC temperature and voltage values when the lockout occurred.
  • Page 60: Dxm2 Process Flow Chart

    Tranquility 30 Digital ( TE) Series IOM - 60Hz HFC-410A ® R e v . : O c t o b e r 5 , 2 0 2 1 DXM2 Process Flow Chart ⚠ ⚠ WARNING! WARNING! HAZARDOUS VOLTAGE! DISCONNECT ALL ELECTRIC POWER INCLUDING REMOTE DISCONNECTS BEFORE SERVICING.
  • Page 61: Functional & Performance Troubleshooting

    Tranquility 30 Digital ( TE) Series IOM - 60Hz HFC-410A ® R e v . : O c t o b e r 5 , 2 0 2 1 Functional Troubleshooting Fault Htg Clg Possible Cause Solution Check Line Voltage circuit breaker and disconnect Check for line voltage between L1 and L2 on the contactor Main Power Problems Green status LED off...
  • Page 62 (ClimaDry) - Code 11 or ClimaDry Find and eliminate restriction - increase return duct Too high of external static - check static vs blower table Restricted return air flow Plugged air filter Replace air filter and/or grille size Too much cold vent air - bring entering air temp within Find and eliminate restriction - increase return duct Air temperature out of range Check power supply and 24VAC voltage before and during...
  • Page 63 Tranquility 30 Digital ( TE) Series IOM - 60Hz HFC-410A ® R e v . : O c t o b e r 5 , 2 0 2 1 Performance Troubleshooting Symptom Htg Clg Possible Cause Solution Dirty filter Replace or clean Check for dirty air filter and clean or replace Reduced or no air flow Check fan motor operation and airflow restrictions...
  • Page 64 Non-condensables insystem Vacuum system and reweigh in charge Restricted metering device Check superheat and subcooling per chart - replace Check pump operation or water valve operation/setting Reduced water flow Tranquility 30 Digital ( TE) Series IOM - 60Hz HFC-410A ® Plugged strainer or filter - clean or replace in heating Check water flow adjust to proper flow rate...
  • Page 65: Troubleshooting Form

    Tranquility 30 Digital ( TE) Series IOM - 60Hz HFC-410A ® R e v . : O c t o b e r 5 , 2 0 2 1 Troubleshooting Form Packaged Water-to-Air RP929 Troubleshooting Form Customer: Loop Type: Startup Date: Model #: Serial #: Antifreeze Type &...
  • Page 66: Warranty

    Tranquility 30 Digital ( TE) Series IOM - 60Hz HFC-410A ® R e v . : O c t o b e r 5 , 2 0 2 1 Warranty G e o t h e r m a l H e a t i n g a n d C o o l i n g...
  • Page 67 Tranquility 30 Digital ( TE) Series IOM - 60Hz HFC-410A ® R e v . : O c t o b e r 5 , 2 0 2 1 Notes: c l i m a t e m a s t e r . c o m...
  • Page 68: Revision History

    97B0045N04 ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time for order may be changed without notice and may not be as described herein. Please contact ClimateMaster’s Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications.

Table of Contents