Tranquility ® (TY) Series Table of Contents Model Nomenclature General Information Unit Physical Data Horizontal Installation Field Conversion of Air Discharge Horizontal Installation Vertical Installation Piping Installation Water-Loop Heat Pump Applications Ground-Loop Heat Pump Applications Ground-Loop and Ground Water Heat Pump Applications Ground-Water Heat Pump Applications Water Quality Standards...
Page 2
C L I M AT E M A S T E R WAT E R - S O U R C E H E AT P U M P S 22 ( TY ) Series Tranquility ® R e v . : J u l y 8 , 2 0 2 1 This Page Intentionally Left Blank C l i m a t e M a s t e r Wa t e r - S o u r c e H e a t P u m p s...
C L I M AT E M A S T E R WAT E R - S O U R C E H E AT P U M P S 22 ( TY ) Series Tranquility ® R e v . : J u l y 8 , 2 0 2 1 Unit Physical Data Tranquility 22 Two-Stage (TY) Series (60 Hz)
T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y 22 ( TY ) Series Tranquility ®...
Page 8
UV based anti-bacterial systems may damage (e.g. louvered door). Therefore, filter rails are the industry coated air coils. standard and are included on ClimateMaster commercial heat pumps for the purposes of holding the filter only. For ducted return applications, the filter rail must be removed and replaced with a duct flange or filter frame.
C L I M AT E M A S T E R WAT E R - S O U R C E H E AT P U M P S 22 ( TY ) Series Tranquility ® R e v . : J u l y 8 , 2 0 2 1 Horizontal Installation Condensate Piping - Horizontal Units - A condensate Condensate drain connection is a rubber coupling that...
(e.g. louvered door). Therefore, filter rails are the industry standard and are included on ClimateMaster commercial heat pumps for the purposes of holding the filter only. For ducted return applications, the filter rail must be removed and replaced with a duct flange or filter frame.
Page 12
C L I M AT E M A S T E R WAT E R - S O U R C E H E AT P U M P S 22 ( TY ) Series Tranquility ® R e v . : J u l y 8 , 2 0 2 1 Vertical Installation, Cont’d.
Tighten steel fittings as necessary. Length (2 ft [0.6m] Length Standard) Optional pressure-rated hose assemblies designed specifically for use with ClimateMaster units are available. Similar hoses can be obtained from alternate suppliers. Supply and return hoses are fitted with swivel-joint Accesorio Accesorio fittings at one end to prevent kinking during installation.
[2.9 and 4.5 l/m per kW] of cooling capacity. mechanical room plumbing. Consideration should be given ClimateMaster recommends 3 gpm per ton [3.9 l/m per to insulating the piping surfaces to avoid condensation. kW] for most applications of water loop heat pumps. To...
C L I M AT E M A S T E R WAT E R - S O U R C E H E AT P U M P S 22 ( TY ) Series Tranquility ® R e v . : J u l y 8 , 2 0 2 1 Ground-Loop and Ground Water Heat Pump Applications Ground-Loop Heat Pump Applications Typical Closed Loop with Central Pumping...
T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y 22 ( TY ) Series Tranquility ®...
Page 18
C L I M AT E M A S T E R WAT E R - S O U R C E H E AT P U M P S 22 ( TY ) Series Tranquility ® R e v . : J u l y 8 , 2 0 2 1 Ground-Water Heat Pump Applications, Cont’d.
20 mesh] size. The ClimateMaster Water Quality Table provides water quality requirements for ClimateMaster coaxial heat exchangers and fluid coolers. The water should be evaluated by an independent testing facility comparing to this Table and when properties are outside of these requirements, an external secondary heat exchanger must be used to isolate the equipment from the unsuitable water.
Figure 12 to change the setting to 10°F [-12.2°C] refrigerant temperature, a more suitable temperature when using an antifreeze solution. All ClimateMaster units operating with entering water temperatures below 60°F [15.6°C] must include the optional water/refrigerant circuit insulation package to prevent internal condensation.
Figures 19 and 20 illustrate Acc2 Relay typical slow closing water control valve wiring for Taco 500 series (ClimateMaster P/N AVM) and Taco SBV series valves. Slow closing valves take approximately AO1 Gnd T2 T2 T3 T3 T4 T4...
IOM and or unit wiring measurement. Position the thermostat back plate against diagram. Practically any heat pump thermostat will work the wall so that it appears level and so the thermostat with ClimateMaster units, provided it has the correct Outdoor Sensor (Optional) wires protrude through the middle of the back plate.
C L I M AT E M A S T E R WAT E R - S O U R C E H E AT P U M P S 22 ( TY ) Series Tranquility ® R e v . : J u l y 8 , 2 0 2 1 Blower Performance Data TY Standard Unit Cooling Mode...
R e v . : J u l y 8 , 2 0 2 1 TY Series Wiring Diagram Matrix All current diagrams can be located online at climatemaster.com. Click ‘Commercial Professional’ (go to ‘Resources/literature/wiring diagrams’ in the upper right), use part numbers below to look...
T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y 22 ( TY ) Series Tranquility ®...
Page 30
C L I M AT E M A S T E R WAT E R - S O U R C E H E AT P U M P S 22 ( TY ) Series Tranquility ® R e v . : J u l y 8 , 2 0 2 1 DXM2 Controls, Cont’d.
Page 31
T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y 22 ( TY ) Series Tranquility ®...
C L I M AT E M A S T E R WAT E R - S O U R C E H E AT P U M P S 22 ( TY ) Series Tranquility ® R e v . : J u l y 8 , 2 0 2 1 DXM2 Layout and Connections Communicating Service tool...
ClimaDry II to operate properly. 4. Verify that all strainers are in place (ClimateMaster recommends a strainer with a #20 stainless steel wire mesh). Start the pumps, and systematically check each vent to ensure that all air is bled from the system.
5. Two factors determine the operating limits of c. Check for warm air delivery within a few minutes ClimateMaster heat pumps, (a) return air temperature, after the unit has begun to operate. and (b) water temperature. When any one of these factors is at a minimum or maximum level, the other d.
T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y 22 ( TY ) Series Tranquility ®...
Page 40
C L I M AT E M A S T E R WAT E R - S O U R C E H E AT P U M P S 22 ( TY ) Series Tranquility ® R e v . : J u l y 8 , 2 0 2 1 Unit Operating Conditions, Cont’d.
Page 41
T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y 22 ( TY ) Series Tranquility ®...
C L I M AT E M A S T E R WAT E R - S O U R C E H E AT P U M P S 22 ( TY ) Series Tranquility ® R e v . : J u l y 8 , 2 0 2 1 Preventive Maintenance Water Coil Maintenance - (Direct ground water Condensate Drain - In areas where airborne bacteria...
Page 43
T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y 22 ( TY ) Series Tranquility ®...
Page 44
C L I M AT E M A S T E R WAT E R - S O U R C E H E AT P U M P S 22 ( TY ) Series Tranquility ® R e v . : J u l y 8 , 2 0 2 1 Troubleshooting, Cont’d.
C L I M AT E M A S T E R WAT E R - S O U R C E H E AT P U M P S 22 ( TY ) Series Tranquility ® R e v . : J u l y 8 , 2 0 2 1 Functional Troubleshooting Fault Clg Possible Cause...
Page 47
T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y 22 ( TY ) Series Tranquility ®...
C L I M AT E M A S T E R WAT E R - S O U R C E H E AT P U M P S 22 ( TY ) Series Tranquility ® R e v . : J u l y 8 , 2 0 2 1 Performance Troubleshooting Symptom Htg Clg Possible Cause...
Page 49
Check pump operation or water valve operation/setting Reduced water flow Plugged strainer or filter - clean or replace in heating T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y Check water flow adjust to proper flow rate Water temperature out of range Bring water temp within design parameters...
C L I M AT E M A S T E R WAT E R - S O U R C E H E AT P U M P S 22 ( TY ) Series Tranquility ® R e v . : J u l y 8 , 2 0 2 1 Start-Up Log Sheet Installer: Complete unit and system checkout and follow unit start-up procedures in the IOM.
Model Number: ________________________ Serial Number: ________________________ T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y Date: ________________________ Packaged Unit Refrigeration Schematic 22 ( TY ) Series...
T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y 22 ( TY ) Series Tranquility ®...
Page 54
C L I M AT E M A S T E R WAT E R - S O U R C E H E AT P U M P S 22 ( TY ) Series Tranquility ® R e v . : J u l y 8 , 2 0 2 1 Notes: C l i m a t e M a s t e r Wa t e r - S o u r c e H e a t P u m p s...
Page 55
T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y 22 ( TY ) Series Tranquility ®...
ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time for order may be changed without notice and may not be as described herein. Please contact ClimateMaster’s Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications.