ClimateMaster Tranquility TY Series Installation, Operation, Maintenance Manual

ClimateMaster Tranquility TY Series Installation, Operation, Maintenance Manual

Water -source heat pumps

Advertisement

Advertisement

Table of Contents
loading

Summary of Contents for ClimateMaster Tranquility TY Series

  • Page 1: Table Of Contents

    Tranquility ® (TY) Series Table of Contents Model Nomenclature General Information Unit Physical Data Horizontal Installation Field Conversion of Air Discharge Horizontal Installation Vertical Installation Piping Installation Water-Loop Heat Pump Applications Ground-Loop Heat Pump Applications Ground-Loop and Ground Water Heat Pump Applications Ground-Water Heat Pump Applications Water Quality Standards...
  • Page 2 C L I M AT E M A S T E R WAT E R - S O U R C E H E AT P U M P S 22 ( TY ) Series Tranquility ® R e v . : J u l y 8 , 2 0 2 1 This Page Intentionally Left Blank C l i m a t e M a s t e r Wa t e r - S o u r c e H e a t P u m p s...
  • Page 3: Model Nomenclature

    T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y 22 ( TY ) Series Tranquility ®...
  • Page 4: General Information

    C L I M AT E M A S T E R WAT E R - S O U R C E H E AT P U M P S 22 ( TY ) Series Tranquility ® R e v . : J u l y 8 , 2 0 2 1 General Information ⚠...
  • Page 5 T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y 22 ( TY ) Series Tranquility ®...
  • Page 6: Unit Physical Data

    C L I M AT E M A S T E R WAT E R - S O U R C E H E AT P U M P S 22 ( TY ) Series Tranquility ® R e v . : J u l y 8 , 2 0 2 1 Unit Physical Data Tranquility 22 Two-Stage (TY) Series (60 Hz)
  • Page 7: Horizontal Installation

    T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y 22 ( TY ) Series Tranquility ®...
  • Page 8 UV based anti-bacterial systems may damage (e.g. louvered door). Therefore, filter rails are the industry coated air coils. standard and are included on ClimateMaster commercial heat pumps for the purposes of holding the filter only. For ducted return applications, the filter rail must be removed and replaced with a duct flange or filter frame.
  • Page 9: Field Conversion Of Air Discharge

    T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y 22 ( TY ) Series Tranquility ®...
  • Page 10: Horizontal Installation

    C L I M AT E M A S T E R WAT E R - S O U R C E H E AT P U M P S 22 ( TY ) Series Tranquility ® R e v . : J u l y 8 , 2 0 2 1 Horizontal Installation Condensate Piping - Horizontal Units - A condensate Condensate drain connection is a rubber coupling that...
  • Page 11: Vertical Installation

    (e.g. louvered door). Therefore, filter rails are the industry standard and are included on ClimateMaster commercial heat pumps for the purposes of holding the filter only. For ducted return applications, the filter rail must be removed and replaced with a duct flange or filter frame.
  • Page 12 C L I M AT E M A S T E R WAT E R - S O U R C E H E AT P U M P S 22 ( TY ) Series Tranquility ® R e v . : J u l y 8 , 2 0 2 1 Vertical Installation, Cont’d.
  • Page 13: Piping Installation

    Tighten steel fittings as necessary. Length (2 ft [0.6m] Length Standard) Optional pressure-rated hose assemblies designed specifically for use with ClimateMaster units are available. Similar hoses can be obtained from alternate suppliers. Supply and return hoses are fitted with swivel-joint Accesorio Accesorio fittings at one end to prevent kinking during installation.
  • Page 14: Water-Loop Heat Pump Applications

    [2.9 and 4.5 l/m per kW] of cooling capacity. mechanical room plumbing. Consideration should be given ClimateMaster recommends 3 gpm per ton [3.9 l/m per to insulating the piping surfaces to avoid condensation. kW] for most applications of water loop heat pumps. To...
  • Page 15: Ground-Loop Heat Pump Applications

    T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y 22 ( TY ) Series Tranquility ®...
  • Page 16: Ground-Loop And Ground Water Heat Pump Applications

    C L I M AT E M A S T E R WAT E R - S O U R C E H E AT P U M P S 22 ( TY ) Series Tranquility ® R e v . : J u l y 8 , 2 0 2 1 Ground-Loop and Ground Water Heat Pump Applications Ground-Loop Heat Pump Applications Typical Closed Loop with Central Pumping...
  • Page 17: Ground-Water Heat Pump Applications

    T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y 22 ( TY ) Series Tranquility ®...
  • Page 18 C L I M AT E M A S T E R WAT E R - S O U R C E H E AT P U M P S 22 ( TY ) Series Tranquility ® R e v . : J u l y 8 , 2 0 2 1 Ground-Water Heat Pump Applications, Cont’d.
  • Page 19: Water Quality Standards

    20 mesh] size. The ClimateMaster Water Quality Table provides water quality requirements for ClimateMaster coaxial heat exchangers and fluid coolers. The water should be evaluated by an independent testing facility comparing to this Table and when properties are outside of these requirements, an external secondary heat exchanger must be used to isolate the equipment from the unsuitable water.
  • Page 20: Electrical - Line Voltage

    C L I M AT E M A S T E R WAT E R - S O U R C E H E AT P U M P S 22 ( TY ) Series Tranquility ® R e v . : J u l y 8 , 2 0 2 1 Electrical –...
  • Page 21: Electrical - Power Wiring

    T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y 22 ( TY ) Series Tranquility ®...
  • Page 22: Electrical - Power & Low Voltage Wiring

    Figure 12 to change the setting to 10°F [-12.2°C] refrigerant temperature, a more suitable temperature when using an antifreeze solution. All ClimateMaster units operating with entering water temperatures below 60°F [15.6°C] must include the optional water/refrigerant circuit insulation package to prevent internal condensation.
  • Page 23: Electrical - Low Voltage Wiring

    Figures 19 and 20 illustrate Acc2 Relay typical slow closing water control valve wiring for Taco 500 series (ClimateMaster P/N AVM) and Taco SBV series valves. Slow closing valves take approximately AO1 Gnd T2 T2 T3 T3 T4 T4...
  • Page 24: Electrical - Low Voltage Wiring For Units Using External

    C L I M AT E M A S T E R WAT E R - S O U R C E H E AT P U M P S 22 ( TY ) Series Tranquility ® R e v . : J u l y 8 , 2 0 2 1 Electrical –...
  • Page 25: Electrical - Thermostat Wiring

    IOM and or unit wiring measurement. Position the thermostat back plate against diagram. Practically any heat pump thermostat will work the wall so that it appears level and so the thermostat with ClimateMaster units, provided it has the correct Outdoor Sensor (Optional) wires protrude through the middle of the back plate.
  • Page 26: Blower Performance Data

    C L I M AT E M A S T E R WAT E R - S O U R C E H E AT P U M P S 22 ( TY ) Series Tranquility ® R e v . : J u l y 8 , 2 0 2 1 Blower Performance Data TY Standard Unit Cooling Mode...
  • Page 27: Ecm Blower Control

    T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y 22 ( TY ) Series Tranquility ®...
  • Page 28: Ty Series Wiring Diagram Matrix

    R e v . : J u l y 8 , 2 0 2 1 TY Series Wiring Diagram Matrix All current diagrams can be located online at climatemaster.com. Click ‘Commercial Professional’ (go to ‘Resources/literature/wiring diagrams’ in the upper right), use part numbers below to look...
  • Page 29: Dxm2 Controls

    T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y 22 ( TY ) Series Tranquility ®...
  • Page 30 C L I M AT E M A S T E R WAT E R - S O U R C E H E AT P U M P S 22 ( TY ) Series Tranquility ® R e v . : J u l y 8 , 2 0 2 1 DXM2 Controls, Cont’d.
  • Page 31 T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y 22 ( TY ) Series Tranquility ®...
  • Page 32: Dxm2 Layout And Connections

    C L I M AT E M A S T E R WAT E R - S O U R C E H E AT P U M P S 22 ( TY ) Series Tranquility ® R e v . : J u l y 8 , 2 0 2 1 DXM2 Layout and Connections Communicating Service tool...
  • Page 33: Dxm2 Controls

    T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y 22 ( TY ) Series Tranquility ®...
  • Page 34 Temp (ºC) Temp (ºF) (kOhm) (kOhm) cool thermostats can be used with the DXM2, as well as -17.8 85.34 131.0 2.99 -17.5 84.00 132.8 2.88 ClimateMaster communicating thermostats (ATC32). -16.9 81.38 134.6 2.77 10.4 61.70 136.4 2.67 12.2 58.40 138.2 2.58...
  • Page 35: Unit Starting And Operating Conditions

    T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y 22 ( TY ) Series Tranquility ®...
  • Page 36: Piping System Cleaning And Flushing

    ClimaDry II to operate properly. 4. Verify that all strainers are in place (ClimateMaster recommends a strainer with a #20 stainless steel wire mesh). Start the pumps, and systematically check each vent to ensure that all air is bled from the system.
  • Page 37: Unit And System Checkout

    T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y 22 ( TY ) Series Tranquility ®...
  • Page 38: Unit Start-Up Procedure

    5. Two factors determine the operating limits of c. Check for warm air delivery within a few minutes ClimateMaster heat pumps, (a) return air temperature, after the unit has begun to operate. and (b) water temperature. When any one of these factors is at a minimum or maximum level, the other d.
  • Page 39: Unit Operating Conditions

    T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y 22 ( TY ) Series Tranquility ®...
  • Page 40 C L I M AT E M A S T E R WAT E R - S O U R C E H E AT P U M P S 22 ( TY ) Series Tranquility ® R e v . : J u l y 8 , 2 0 2 1 Unit Operating Conditions, Cont’d.
  • Page 41 T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y 22 ( TY ) Series Tranquility ®...
  • Page 42: Preventive Maintenance

    C L I M AT E M A S T E R WAT E R - S O U R C E H E AT P U M P S 22 ( TY ) Series Tranquility ® R e v . : J u l y 8 , 2 0 2 1 Preventive Maintenance Water Coil Maintenance - (Direct ground water Condensate Drain - In areas where airborne bacteria...
  • Page 43 T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y 22 ( TY ) Series Tranquility ®...
  • Page 44 C L I M AT E M A S T E R WAT E R - S O U R C E H E AT P U M P S 22 ( TY ) Series Tranquility ® R e v . : J u l y 8 , 2 0 2 1 Troubleshooting, Cont’d.
  • Page 45: Dxm2 Process Flow Chart

    T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y 22 ( TY ) Series Tranquility ®...
  • Page 46: Functional Troubleshooting

    C L I M AT E M A S T E R WAT E R - S O U R C E H E AT P U M P S 22 ( TY ) Series Tranquility ® R e v . : J u l y 8 , 2 0 2 1 Functional Troubleshooting Fault Clg Possible Cause...
  • Page 47 T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y 22 ( TY ) Series Tranquility ®...
  • Page 48: Performance Troubleshooting

    C L I M AT E M A S T E R WAT E R - S O U R C E H E AT P U M P S 22 ( TY ) Series Tranquility ® R e v . : J u l y 8 , 2 0 2 1 Performance Troubleshooting Symptom Htg Clg Possible Cause...
  • Page 49 Check pump operation or water valve operation/setting Reduced water flow Plugged strainer or filter - clean or replace in heating T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y Check water flow adjust to proper flow rate Water temperature out of range Bring water temp within design parameters...
  • Page 50: Start-Up Log Sheet

    C L I M AT E M A S T E R WAT E R - S O U R C E H E AT P U M P S 22 ( TY ) Series Tranquility ® R e v . : J u l y 8 , 2 0 2 1 Start-Up Log Sheet Installer: Complete unit and system checkout and follow unit start-up procedures in the IOM.
  • Page 51: Functional Troubleshooting

    Model Number: ________________________ Serial Number: ________________________ T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y Date: ________________________ Packaged Unit Refrigeration Schematic 22 ( TY ) Series...
  • Page 52: Warranty (U.s. & Canada)

    C L I M AT E M A S T E R WAT E R - S O U R C E H E AT P U M P S 22 ( TY ) Series Tranquility ® R e v . : J u l y 8 , 2 0 2 1 Warranty (U.S.
  • Page 53: Warranty (International)

    T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y 22 ( TY ) Series Tranquility ®...
  • Page 54 C L I M AT E M A S T E R WAT E R - S O U R C E H E AT P U M P S 22 ( TY ) Series Tranquility ® R e v . : J u l y 8 , 2 0 2 1 Notes: C l i m a t e M a s t e r Wa t e r - S o u r c e H e a t P u m p s...
  • Page 55 T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y 22 ( TY ) Series Tranquility ®...
  • Page 56: Revision History

    ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time for order may be changed without notice and may not be as described herein. Please contact ClimateMaster’s Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications.