Tranquility Compact ® Belt Drive (TCH/V) Series Table of Contents Model Nomenclature General Information TCH Physical Data (includes unit w/WSE) TCV Physical Data (includes unit w/WSE) Horizontal Installation TCH Field Conversion of Air Discharge Vertical Installation TCV Field Conversion of Air Discharge TCV072-240 Field Conversion of Air Discharge TCV300 Field Conversion of Air Discharge TCV Field Conversion of Control Box...
Page 2
C L I M A T E M A S T E R W A T E R - S O U R C E H E A T P U M P S Tranquility Compact Belt Drive (TCH/V) Series ®...
C L I M A T E M A S T E R W A T E R - S O U R C E H E A T P U M P S Tranquility Compact Belt Drive (TCH/V) Series ®...
Page 17
A thorough water rinse should (e.g. louvered door). Therefore, fi lter rails are the industry follow. UV based anti-bacterial systems may damage standard and are included on ClimateMaster commercial coated air coils. heat pumps for the purposes of holding the fi lter only.
fl oor level closet or in a small mechanical room. Refer to ClimateMaster will not warrant, or accept responsibility Figure 7 for an illustration of a typical installation. Install for products which fail, have defects, damage or insuffi - units with adequate clearance to allow maintenance and cient performance as a result of improper application.
Length Optional pressure-rated hose assemblies designed (2 ft [0.6m] Length Standard) specifi cally for use with ClimateMaster units are available. Similar hoses can be obtained from alternate suppliers. Supply and return hoses are fi tted with swivel-joint fi ttings at one end to prevent kinking during installation.
2.25 and 3.5 gpm per ton [2.9 and 4.5 l/m per to a common piping system. Any unit plumbing main- kW] of cooling capacity. ClimateMaster recommends 3 tenance work can introduce air into the piping system; gpm per ton [3.9 l/m per kW] for most applications of therefore air elimination equipment is a major portion water loop heat pumps.
20 mesh] size. The ClimateMaster Water Quality Table provides water quality requirements for ClimateMaster coaxial heat exchangers. The water should be evaluated by an Rev.: 5/6/2014 S independent testing facility comparing to this Table and when properties are outside of these requirements, an external secondary heat exchanger must be used to isolate the heat pump heat exchanger from the unsuitable water.
See the specifi c unit wiring temperature when using an antifreeze solution. All diagram for details. ClimateMaster units operating with entering water temperatures below 59°F [15°C] must include the Low Voltage VA Ratings optional water/refrigerant circuit insulation package to prevent internal condensation.
Page 43
120 Valve high pressure switch shall have a cut-out pressure of 300 psig and a cut-in pressure of 250 psig. This pressure switch can be ordered from ClimateMaster with a 1/4” internal fl are connection as part number 39B0005N02. Thermostat...
Practically any heat pump thermostat back plate against the wall so that it appears level and will work with ClimateMaster units, provided it has so the thermostat wires protrude through the middle the correct number of heating and cooling stages.
LT2 of 30°F or 10°F [-1°F or -12°C] (refrigerant temperature). Note: This jumper should only be Table 6b: DXM LED And Alarm Relay Operations clipped under extenuating circumstances, as recommended by ClimateMaster technical Status LED Test LED Fault LED...
Page 51
T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y Tranquility Compact Belt Drive (TCH/V) Series ®...
4. Verify that all strainers are in place (ClimateMaster prior to any fi nishing of the interior space or before recommends a strainer with a #20 stainless steel access to all connections is limited.
Adjust the thermostat to the lowest setting. 5. Two factors determine the operating limits of Place the thermostat mode switch in the “HEAT” ClimateMaster heat pumps, (a) return air temperature, position. and (b) water temperature. When any one of these b.
Page 71
T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y Tranquility Compact Belt Drive (TCH/V) Series ®...
97B0084N01 ClimateMaster works continually to improve its products. As a result, the design and specifi cations of each product at the time for order may be changed without notice and may not be as described herein. Please contact ClimateMaster’s Customer Service Department at 1-405-745-6000 for specifi c information on the current design and specifi...