Codes
Code 1
(cont.)
Coding in the delivered condition
Buffer cylinder charging to sensor
36:3
The boiler charges the heating wa-
ter buffer cylinder up to buffer tem-
perature sensor 3.
Buffer cylinder charging up to temperature
37:60
The boiler charges the heating wa-
ter buffer cylinder until the temper-
ature of 60 °C is reached at the se-
lected sensor (code "36:1-5", buf-
fer cylinder group).
Boiler start, sensor
39:1
If the set system temperature at
the 1st buffer temperature sensor
is undershot, the boiler starts.
Additional heat generator
Available if code "Additional boiler" is set to "Yes".
98
Possible change
36:1
The boiler charges the heating water
buffer cylinder up to buffer tempera-
ture sensor 1 (top).
36:2
The boiler charges the heating water
buffer cylinder up to buffer tempera-
ture sensor 2.
36:4
The boiler charges the heating water
buffer cylinder up to buffer tempera-
ture sensor 4.
36:5
The boiler charges the heating water
buffer cylinder up to buffer tempera-
ture sensor 5.
37:30
Setting range in °C
to
37:100
39:2
If the set system temperature at the
2nd buffer temperature sensor (top)
is undershot, the boiler starts.
39:3
If the set system temperature at the
3rd buffer temperature sensor is un-
dershot, the boiler starts.
39:4
If the set system temperature at the
4th buffer temperature sensor is un-
dershot, the boiler starts.
39:5
If the set system temperature at the
5th buffer temperature sensor is un-
dershot, the boiler starts.
For code "Additional boiler", see Hardware group.