Viessmann Vitoligno 300-H Installation And Service Instructions For Contractors page 96

Boiler for woodchips and pellets
Hide thumbs Also See for Vitoligno 300-H:
Table of Contents

Advertisement

Codes
Code 1
(cont.)
Coding in the delivered condition
Light barrier delay screw conveyor
0F:5
Delay of 0.5 seconds
Feed screw conveyor heat-up cycle
14:...
Start cycle of the feed screw con-
veyor in % after boiler ignition
Feed screw conveyor maximum cycle
15:...
Max. cycle limit of feed screw con-
veyor in %
Vacuum module cycle - ON
28:20
Cycle of 20 seconds
Vacuum module cycle - OFF
29:10
Cycle of 10 seconds
Vacuum module pre-flushing time
2A:10
Pre-flushing time of 10 seconds
Vacuum module post-flushing time
2B:10
Post-flushing time of 10 seconds
Day hopper idle runtime
2C:15
Idle runtime, 15 min
Screw conveyor delay
2E:2
Delay of 2 seconds
Light barrier delay transfer discharge
2F:5
Delay of 5 seconds
Discharge cycle - ON
30:5
Discharge cycle of 5 seconds
Discharge cycle - OFF
31:0
Discharge cycle of 0 seconds
96
Possible change
0F:0
Setting range in tenths of seconds
to
0F:100
14:1
Setting range in %
to
14:100
15:1
Setting range in %
to
15:100
28:2
Setting range in seconds
to
28:600
29:0
Setting range in seconds
to
29:250
2A:0
Setting range in seconds
to
2A:60
2B:0
Setting range in seconds
to
2B:60
2C:1
Setting range in min
to
2C:600
2E:0
Setting range in seconds
to
2E:100
2F:0
Setting range in seconds
to
2F:300
30:2
Setting range in seconds
to
30:250
31:0
Setting range in seconds
to
31:1000