Specification
(cont.)
Fuel
Rated heating output
Installed weights
Boiler without water or
Feed (without shut-off gate valve/rotary lock valve)
Ash box
Thermal insulation
Boiler with water and
Feed (without shut-off gate valve/rotary lock valve)
Ash box
Thermal insulation
Capacity
Boiler water
Ash box
Protection class
IP rating to EN 60529; ensure through design/installation.
Type of operation to EN 60730-1
Operation of the boiler
Permiss. ambient temperature
During operation
(Use in boiler rooms, standard ambient conditions)
During storage and transport
Electrical data
Rated voltage
Rated frequency
Max. rated current
Power consumption
Ignition
Ash removal
Feed
Flue gas fan
Grate drive
Heat exchanger cleaning
Boiler at Q
N
Boiler at Q
min
Boiler on standby
Rated relay output breaking capacity at 230 V
Heating circuit pumps
Circulation pump for cylinder heating
Solar circuit pump, as alternative to heating circuit pump M2
DHW circulation pump
Central fault message
Mixer motor
Discharge motor, room discharge/silo, mole
Specification
Wood-
chips
kW
50
kg
1077
kg
1287
l
210
l
45
kg
18
I
IP 20
Type 1 B
Non-con-
densing
°C
0 to +35
°C
20 to +65
V
400
Hz
50
A
10
W
1400
W
25
W
380
W
100
W
14
W
14
W
234
W
122
W
26
A
4 (2)
A
4 (2)
A
4 (2)
A
4 (2)
A
4 (2)
A
0.2 (0.1)
W
Max. 200
Wood-
chips
60
1077
1287
210
45
18
I
IP 20
Type 1 B
Non-con-
densing
0 to +35
20 to +65
400
50
10
1400
25
380
100
14
14
259
122
26
4 (2)
4 (2)
4 (2)
4 (2)
4 (2)
0.2 (0.1)
Max. 200
155