Viessmann Vitoligno 300-H Installation And Service Instructions For Contractors page 97

Boiler for woodchips and pellets
Hide thumbs Also See for Vitoligno 300-H:
Table of Contents

Advertisement

Code 1
(cont.)
Coding in the delivered condition
Discharge delay
32:5
Delay of 5 seconds
External charging cycle - ON
40:5
External charging cycle of
5 seconds
External charging cycle - OFF
41:0
External charging cycle of
0 seconds
External charging delay
42:5
Delay to external charging
5 seconds
Discharge, reversing interval
BD:...
Interval: Discharge system
changes direction of rotation
Discharge, preferred direction
BE:...
Preferred direction of discharge
Delay, hydraulic drive unit
C1:...
Delay to hydraulic drive unit
Transverse screw conveyor, emergency mode delay
C2:...
Emergency mode delay of the
transverse screw conveyor
Hydraulic drive unit, emergency mode
C3:2
Emergency mode delay of the hy-
draulic drive unit
Buffer
Coding
Coding in the delivered condition
Maximum set temperature, buffer cylinder
34:85
Max. average temperature of the
heating water buffer cylinder, 85 °C
(upper limit of control range)
Minimum set temperature, buffer cylinder
35:60
Min. set temperature of the heating
water buffer cylinder, 60 °C (lower
limit of control range)
Possible change
32:0
Setting range in seconds
to
32:300
40:2
Setting range in seconds
to
40:250
41:0
Setting range in seconds
to
41:1000
42:0
Setting range in seconds
to
42:300
BD:0
Setting range in seconds
to
BD:300
BE:0
0 = No
to
1 = Yes
BE:1
C1:0
Setting range in seconds
to
C1:300
C2:0
Setting range in seconds
to
C2:1000
C3:0
Setting range in seconds
to
C3:250
Possible change
34:30
Setting range in °C
to
34:100
35:30
Setting range in °C
to
35:100
Codes
97