High limit safety cut-out
Triggering the function
If the boiler water temperature exceeds 95 °C, the high
limit safety cut-out responds.
Cancelling the function
Note
The high limit safety cut-out can only be reset
(unlocked) once the boiler water temperature has
reached approx. 70 °C.
!
Please note
If this function is not reset, it inhibits the safety
equipment function and can result in system
damage.
Reset the high limit safety cut-out.
Whenever the high limit safety cut-out has been
triggered, check afterwards that the thermally
activated safety valve is reset.
B
A
Fig. 69
Sensors
Sensor type Pt1000:
Flow temperature sensor
Buffer temperature sensor
Return temperature sensor
Flue gas temperature sensor
Outside temperature sensor
Connection
See chapter "Connection and wiring diagram" from
page 142.
(cont.)
Note
The high limit safety cut-out can only be reset man-
ually.
1. Move cover
on the programming unit to the
A
right.
2. Press green button
B
out.
A faint "click" will be audible; the high limit safety
cut-out is reset.
3. Close cover
on the programming unit.
A
4. Acknowledge excess temperature at the program-
ming unit with
.
d
Curve of the sensor from the extension kit for heating
circuit with mixer:
Extension kit installation instructions
Maintenance
of the high limit safety cut-