Viessmann Vitoligno 300-H Installation And Service Instructions For Contractors page 80

Boiler for woodchips and pellets
Hide thumbs Also See for Vitoligno 300-H:
Table of Contents

Advertisement

Commissioning, inspection, maintenance
Checking the heat exchanger cleaning
2.
A
Fig. 62
1. Remove the top casing panel.
2. Loosen all 4 nuts
A
the side.
Note
The nuts do not have to be removed.
3. Lift off maintenance cover
Note
The maintenance cover can be set down on the
top casing panel.
80
1.
3.
B
and swivel bolts with nuts to
.
B
(cont.)
4. Check the heat exchanger cleaning
Switch on the system. Do not start the boiler.
Switch the heat exchanger cleaning by means of
an actuator test.
Isolate the system from the power supply and
check that it is no longer live.
Safeguard the system against reconnection.
Note
The heat exchanger cleaning can be switched via
"Actuator test" in the "Service" menu. See
page 113.