Viessmann Vitoligno 300-H Installation And Service Instructions For Contractors page 95

Boiler for woodchips and pellets
Hide thumbs Also See for Vitoligno 300-H:
Table of Contents

Advertisement

Code 1
(cont.)
Coding in the delivered condition
Ash removal interval
57:...
Interval, ash removal in minutes
Heat exchanger ON
58:20
Pulse time of 20 seconds
Heat exchanger pause
59:60
Pause time of 60 minutes
Boiler return min.
7B:65
Boiler return minimum temperature
65 °C
Boiler run-on time
8C:...
Min. run-on time in minutes before
the boiler switches off.
Flue gas filter, maximum voltage
DA:...
Max. voltage of the electrostatic
flue gas filter
Charging
Different codes will be available depending on the set
"Charging scheme".
Coding
Coding in the delivered condition
Dosing hopper idle runtime
02:5
Idle runtime of dosing hopper
5 seconds
Combustion chamber filling time
03:...
Filling time in seconds
Feed screw conveyor filling time
04:...
Filling time in seconds
Light barrier delay dosing hopper
06:10
Delay of 1 second
Possible change
57:0
Setting range in minutes
to
57:1000
58:1
Setting range in seconds
to
58:900
59:0
Setting range in minutes
to
59:900
7B:60
Setting range in °C
to
7B:85
8C:0
Setting range in minutes
to
8C:60
DA:15
Setting range in kV
to
DA:30
Possible change
02:0
Setting range in seconds
to
02:100
03:10
Setting range in seconds
to
03:600
04:5
Setting range in seconds
to
04:600
06:0
Setting range in tenths of seconds
to
06:100
Codes
95

Advertisement

Table of Contents
loading

This manual is also suitable for:

Vh3

Table of Contents