Viessmann Vitoligno 300-H Installation And Service Instructions For Contractors page 111

Boiler for woodchips and pellets
Hide thumbs Also See for Vitoligno 300-H:
Table of Contents

Advertisement

Code 2
(cont.)
Coding in the delivered condition
Screed drying
F1:0
Screed drying not active
DHW (DHW heater)
Coding
Coding in the delivered condition
Set DHW temperature reheating suppression
67:0
Reheating suppression of solar
control unit deactivated
Start hysteresis, DHW
85:0
Pump on: As soon as DHW
DHW
set
Controllers
Note
Changing the controllers is only permitted following
consultation with the manufacturer.
<
actual
- 2.5 K
Possible change
F1:1
Screed drying adjustable, with
to
choice of 6 temperature/time pro-
F1:6
files.
For further information, see chapter
"Screed drying"
Possible change
67:1
DHW set value during active reheat-
to
ing suppression of the solar control
67:90
unit in °C
85:1
Setting range in K
to
Pump on: As soon as DHW 1 to
85:10
10 K below WW
Codes
set
111