Wiring

6
Wiring
6.1

General wiring guidelines

Please note:
}
If short circuits occur between the cable from the output to the load and a supply line, it
will no longer be possible to switch off the load. Possible remedies:
}
Use appropriate wiring to exclude short circuits between the outputs!
}
The actuators may be connected using unshielded cables.
}
The outputs do not need suppression for inductive loads.
}
Use copper wiring.
}
The terminal configuration as stated on the front plate applies for base modules with C-
rail. The terminal configuration as stated in the technical documentation applies for all
other base modules.
6.1.1

Mechanical connection of the base modules

Procedure:
}
Use a flat blade screwdriver (DIN 5264-A)!
}
Strip the wire back 8 mm.
}
If necessary, label the connection level with a colour marker [3].
}
Base module with screw terminals:
}
Base module with cage clamp terminals:
Operating Manual PSSu E F 2DO 2(-T)(-R)
21322-EN-07
Exclude the error by using separate multicore cable for supply voltages
Use dual actuators, e.g. two contactors in series
Use an additional shutdown device such as a main contactor
Use a screwdriver to loosen the screw on the screw terminal [1]
Insert the stripped cable into the round fixing hole [2], as far as it will go.
Tighten up the screw on the screw terminal.
Check that the cable is firmly seated.
Insert the screwdriver [4] into the square hole [1].
Insert the stripped cable into the round fixing hole [2], as far as it will go [5].
Pull out the screwdriver [6].