Preface This document is a translation of the original document. All rights to this documentation are reserved by Pilz GmbH & Co. KG. Copies may be made for internal purposes. Suggestions and comments for improving this documentation will be gratefully received.
General wiring guidelines 6.1.1 Mechanical connection of the base modules Terminal configuration Connecting the module Section 7 Operation Messages Display elements 7.2.1 Display elements for module diagnostics 7.2.2 Display elements for input status Operating Manual PSSu E F 2DI 60-R 1002506-EN-04...
Page 4
Contents Section 8 Technical details Safety characteristic data Section 9 Order reference Product Accessories Operating Manual PSSu E F 2DI 60-R 1002506-EN-04...
Introduction Introduction Validity of documentation This documentation is valid for the product type PSSu E F 2DI 60-R. It is valid until new documentation is published. This operating manual explains the function and operation, describes the installation and provides guidelines on how to connect the product.
It also highlights areas within the text that are of particular import- ance. INFORMATION This gives advice on applications and provides information on special fea- tures. Operating Manual PSSu E F 2DI 60-R 1002506-EN-04...
The product has the following features: 2 galvanically isolated digital inputs LEDs for: – Switch status of each input – Module error For failsafe applications in system environment B (automation system PSS 4000) Operating Manual PSSu E F 2DI 60-R 1002506-EN-04...
Hardware version number – 2D code 3: Labelling strip for the terminal configuration on the base module 4: Status LEDs 5: Name of electronic module 6: Connection level 1 7: Connection level 2 Operating Manual PSSu E F 2DI 60-R 1002506-EN-04...
Page 9
11: Round connection holes (connection levels 1, 2, 3 and 4) for connecting the signal lines 12: Mounting slot for colour marker to label the connection level (connection levels 1, 2, 3 and 4) Operating Manual PSSu E F 2DI 60-R 1002506-EN-04...
The module is supported by PAS4000 from version 1.5.0. We recommend that you always use the latest version (download from www.pilz.com). The PSSu E F 2DI 60-R module may be used in conjunction with the following base mod- ules: PSSu BP 1/8 S-T...
In safety-related applications, please comply with the mission time T in the safety-re- lated characteristic data. When decommissioning, please comply with local regulations regarding the disposal of electronic devices (e.g. Electrical and Electronic Equipment Act). Operating Manual PSSu E F 2DI 60-R 1002506-EN-04...
20 ms if the supply voltage is interrupted. The module provides the following diagnostic data: Start-up error Configuration error FS communication error Bus termination error Temperature error: too warm Input error Operating Manual PSSu E F 2DI 60-R 1002506-EN-04...
PSSu assignment in system environment B Data access is via pre-defined I/O data types: I/O data name I/O data type I/O data element I0(11,21),I1(14,24) FS_I_DI Data: SAFEBOOL Input data I0 ... I1 Operating Manual PSSu E F 2DI 60-R 1002506-EN-04...
5.1.1 Dimensions Base modules with four connection levels: 12,6 mm 8,1 mm 52,1 mm (0.496") (0.319") (2.051") 12,6 mm 72,6 mm (0.496") (2.858") Operating Manual PSSu E F 2DI 60-R 1002506-EN-04...
Push the base module back [2] until you hear it lock into position. On the mounting rail, slide the base module to the left until you hear the two lateral mounting hooks on the adjacent module lock into position [3]. Operating Manual PSSu E F 2DI 60-R 1002506-EN-04...
This is how the base module is coded. The mechanics of the electronic modules are designed for 50 plug in/out cycles. Operating Manual PSSu E F 2DI 60-R 1002506-EN-04...
Installation 5.3.1 Inserting an electronic module Procedure: The electronic module must audibly lock into position [1]. Mark the electronic module using the labelling strips [2]. Schematic representation: Operating Manual PSSu E F 2DI 60-R 1002506-EN-04...
The substitute values are used for the modules' FS outputs, with Valid Bits = FALSE. CAUTION! Sparking can cause interference and errors! Only change the module when the load is switched off! Operating Manual PSSu E F 2DI 60-R 1002506-EN-04...
– Insert the stripped cable into the round fixing hole [2], as far as it will go [5]. – Pull out the screwdriver [6]. – Check that the cable is firmly seated. Operating Manual PSSu E F 2DI 60-R 1002506-EN-04...
Page 20
To crimp the ferrules you can use crimp pliers (crimp form A or C) conforming to EN 60947-1, such as the PZ 1.5 or PZ 6.5 from Weidmüller, for example. – Maximum torque setting: 0.8 Nm Operating Manual PSSu E F 2DI 60-R 1002506-EN-04...
12-22: n.c. 13-23: C-rail supply (13-23-16-26 linked within the base module) 14: Input I1+ 24: Input I1- 15-25: n.c 16-26: C-rail supply (13-23-16-26 linked within the base module) n.c. = not connected Operating Manual PSSu E F 2DI 60-R 1002506-EN-04...
+ 60 V + 60 V I1 + I1 - + 60 V I0 + I0 - + 60 V I1 + I1 - Input device with homogenous channels + 60 V Operating Manual PSSu E F 2DI 60-R 1002506-EN-04...
Page 23
Wiring Input device with diverse channels + 60 V + 60 V Operating Manual PSSu E F 2DI 60-R 1002506-EN-04...
LED on LED off 7.2.1 Display elements for module diagnostics The module has an LED for displaying module errors ("Err" LED). Meaning Name Colour Status - - - No error Module error Operating Manual PSSu E F 2DI 60-R 1002506-EN-04...
Each input is assigned an LED for displaying the input status (LEDs "11", "21", "14" and "24"). Meaning Designa- Colour Status Signal Input Terminal tion - - - 0 signal 11/21 (Input 1) Green 1 signal - - - 0 signal 14/24 (Input 2) Green 1 signal Operating Manual PSSu E F 2DI 60-R 1002506-EN-04...
Storage temperature In accordance with the standard EN 60068-2-1/-2 Temperature range -40 - 70 °C Climatic suitability In accordance with the standard EN 60068-2-78 Humidity 93 % r. h. at 40 °C Operating Manual PSSu E F 2DI 60-R 1002506-EN-04...
Page 27
Housing IP20 Terminals IP20 Mounting area (e.g. control cabinet) IP51 Mechanical data Material Bottom Front Coding Mounting type plug-in Dimensions Height 76 mm Width 12,6 mm Depth 60,2 mm Weight 45 g Operating Manual PSSu E F 2DI 60-R 1002506-EN-04...
A safety function's SIL/PL values are not identical to the SIL/PL values of the units that are used and may be different. We recommend that you use the PAScal software tool to calculate the safety function's SIL/PL values. Operating Manual PSSu E F 2DI 60-R 1002506-EN-04...
PSSu BP-C1 1/12 S-T Base module with C-rail and screw terminals, T-type 314 622 PSSu BP-C1 1/12 C Base module with C-rail and cage clamp terminals 312 623 PSSu BP-C1 1/12 C-T Base module with C-rail and cage clamp terminals, T-type 314 623 Operating Manual PSSu E F 2DI 60-R 1002506-EN-04...
Page 30
Front cover Support Technical support is available from Pilz round the clock. Americas Australia Scandinavia Brazil +61 3 95600621 +45 74436332 +55 11 97569-2804 Spain Canada Europe +34 938497433 +1 888-315-PILZ (315-7459) Austria Switzerland Mexico +43 1 7986263-0 +41 62 88979-30...
Need help?
Do you have a question about the PSSu E F 2DI 60-R and is the answer not in the manual?
Questions and answers