Bartec APEXmv 07-37A2-2211 730 Series Operating Instructions Manual page 67

Ex p control unit
Table of Contents

Advertisement

Ex p configuration
8.3.2.3 Setting the "Ex p parameters / characteristics"
8.3.2.4 Setting the "Ex p parameters / enclosure parameters"
Page 66 of 80
WARNING
RISK OF DEATH OR INJURY CAUSED BY SETTING THE CHARACTERISTICS
INCORRECTLY.
The explosion protection is no longer guaranteed.
 Check the type number and corresponding characteristics of the
pressure monitor.
If the Ex p control unit is in programming mode (parameter switch
has been activated and a password entered), the measurement
units are displayed in mm.
Settings are entered in mm.
01-37A2-7D0005_MV_Manual_Exp-Control-Unit_2021005_0_en.docx
The particular pressure monitor
installed is defined in the
"Characteristics" tab.
This must be correctly adjusted in
order to correctly calculate the purge
time.
The pressure monitor used can be
selected by clicking the button ( ).
The selection table is described in
chapter 7.8.1.3.
The internal volume of the pressurized
equipment is defined in the "
Enclosure parameters" tab.
Ex p Control unit
APEX
mv
Rev. 0