Electrical connections
6.2.1.6 Terminal row "X6"
Page 36 of 80
ATTENTION
MATERIAL DAMAGE DUE TO INCORRECT PRE-FUSING.
Valve or control electronics may be damaged.
 Operate the digital outlet valve only with a 1.0 A pre-fuse and the
proportional outlet valve only with a 1.6 A pre-fuse.
Terminal
Connection
1
Pre-fuse
2
Pre-fuse
3
Valve +
4
Valve -
5
Valve - PE
Connection of the original programming cable
6
L1
GN
7
L2
GNWH
8
L3
OG
9
L4
OGWH
01-37A2-7D0005_MV_Manual_Exp-Control-Unit_2021005_0_en.docx
The terminal row X6 is used to connect
the outlet valve and the accompanying
valve fuse. Furthermore, the terminal
points 6 – 9 are intended for the LAN
connection cable.
Function
Connection pre-fuse valve
Connection pre-fuse valve
+ conductor valve
GND valve
PE valve
Send, negative
Send, positive
Receive, negative
Receive, positive
Ex p Control unit
APEX
mv
Rev. 0