Bartec APEXmv 07-37A2-2211 730 Series Operating Instructions Manual page 35

Ex p control unit
Table of Contents

Advertisement

Electrical connections
6.2.1.2 Terminal row "X5"
6.2.1.3 Terminal row "X8"
Page 34 of 80
Terminal
Connection
1
K3 – COM
2
K3 – NO
3
K3 – NC
4 / 5
PE
6
K4 – COM
7
K4 – NO
8
K4 – NC
ATTENTION
MATERIAL DAMAGE DUE TO OVERCURRENT IN THE CONTROL ELECTRONICS.
Welding of the enabling relays or destruction of the electronics by inductive
loads.
 The Ex p enable (Relay K1, X8 terminal 2 and 3) can only be operated in
conjunction with a mains fuse (max 5 A, 1,500 A switching capacity,
fast).
 Supplement inductive loads with suitable interference suppression
measures. See chapter 6.1.4.
The supply voltage is connected to terminal row X8.
The application within the pressurized enclosure is enabled
by the Ex p control unit. There may be no voltage in the
pressurized enclosure when the Ex p control unit is
deactivated.
The Ex p enable can switch a maximum of one circuit of one
phase with neutral conductor and can be loaded with a maximum of 5 A. If the
current load within the pressurized enclosure has more than 5 A or more than
one phase, this must be implemented with a separately certified Ex d
preconductor which is controlled by the Ex p control unit.
Terminal
Connection
1
PE
2
L´ (+)
3
N´ (-)
01-37A2-7D0005_MV_Manual_Exp-Control-Unit_2021005_0_en.docx
The Ex p control unit has one floating
changeover contact K3 and one floating
changeover contact K4 for signaling and
processing signals. The associated switching
function can be set in the Ex p control unit via
the WEB interface and is freely programmable.
The maximum switching current is 1 A.
Function
Common contact
Normally open contact
Normally closed contact
Common contact
Normally open contact
Normally closed contact
Function
PE power supply
Enable phase Ex p device
Enable neutral Ex p device
Ex p Control unit
APEX
mv
Rev. 0