Bartec APEXmv 07-37A2-2211 730 Series Operating Instructions Manual page 64

Ex p control unit
Table of Contents

Advertisement

Ex p Control unit
APEX
mv
8.3.1.3 Setting the "Ex p parameters / pressure parameters"
Rev. 0
The pressure parameters to be observed are part of IEC / EN 60079-2.
Furthermore, the pressure parameters are application-dependent and
must be checked during initial commissioning.
The following values can be applied as a basic setting:
po = 2.5 mbar (250 Pa)
p1 = 1.0 mbar (100 Pa)
p2 = 1.5 mbar (150 Pa)
p3 = Determination by chapter 3.2
p4 = Application-dependent, e.g. pressure-sensitive components?
P5 = Application-dependent, e.g. pressure-sensitive components?
 Connect PC with Ex p control unit, activate programming switch
 Login to the WEB interface with the user level
 Call up the Purge parameter / Pressure parameter menu
 Enter and confirm the "po - operating overpressure" parameter
e.g. 250 Pa (2.5 mbar)
The value "po" is the internal operating overpressure of the pressurized
enclosure. This value is monitored by the Ex p control unit and
compensated if necessary.
Pop-up window with display changed value opens
 Confirm pop-up window with changed value
 Enter and confirm pressure parameter "p1 - minimum pressure
e.g. 100 Pa (1.0 mbar)
Pop-up window with display changed value opens
 Confirm pop-up window with changed value
 Enter and confirm pressure parameter "p2 - Pre-alarm"
e.g. 150 Pa (1.5 mbar)
Pop-up window with display changed value opens
 Confirm pop-up window with changed value
... Follow the same procedure for the other pressure parameters
 Deactivate programming switch
01-37A2-7D0005_MV_Manual_Exp-Control-Unit_2021005_0_en.docx
Ex p configuration
Page 63 of 80