Ex p Control unit
APEX
mv
7.8.7.1 Setting "Temperature sensors"
Rev. 0
Procedure
 Connect the computer to the Ex p control unit / control station
 Activate the programming switch
 Log into the WEB interface at the user level
 Select the Extended / sensors menu
 Activate the corresponding button for the required temperature sensor,
e.g. temperature sensor 1, by clicking PT100 or 1000
Manual button changes to
Confirm the pop-up window with changed value
 Select the display unit in °C or °F by clicking and activating the button.
Display changes to
Confirm the pop-up window with changed value
 Select the T-sensors / temperature sensor 1 menu
 The signal for the active sensor is displayed by the green detector
 Save switching value 1
e.g. 25 °C
 Confirm the pop-up window with changed value
 Save switching value 2
e.g. 35 °C
 Confirm the pop-up window with changed value
 Save switching value 3
e.g. 60 °C
 Confirm the pop-up window with changed value
 Save switching hysteresis
e.g. 5 K  functions will be activated and deactivated at a hysteresis
of 5K
 Select a function for switching value 1
e.g. open valve 1  function "Cooling using purging air"
Confirm the pop-up window with changed value
 Select a function for switching value 2
e.g. plain text warning  function "Warning is issued as plain text
message"
 Confirm the pop-up window with changed value
 Select a function for switching value 3
e.g. deactivation of Ex p (K1) and plain text alarm message 
function "Withdrawal of the enable for the Ex p equipment and the issuing
of a plain text alarm message"
 Confirm the pop-up window with changed value.
01-37A2-7D0005_MV_Manual_Exp-Control-Unit_2021005_0_en.docx