CAUTION!
The NetVanta 1560-08-65W is intended for indoor use only. Ethernet, PoE cables, and attached equipment are intended for use within the same building with equipotential
bonding, and not intended to be placed in separate buildings or structures. Failure to deploy as described could result in permanent damage from lightning or other electrical
events and voids the warranty.
f
WARNING!
This equipment is not suitable for use in locations where children are likely to be present.
Installation Overview
To install the switch, you will need to do the following:
1. Mount the switch
2. Connect AC Power
3. Install SFP Modules
Installation Steps
To install the NetVanta 1560-08-65W switch, complete the following steps:
Mount The Switch
The switch can be mounted in a 19-inch rack, on a desk or shelf, or on a wall.
Mounting in a 19-inch Rack
g
NOTE
Mounting brackets are not included. Mounting brackets may be ordered from ADTRAN using the following part number: 1700518F1
To mount the switch into a 19-inch rack, complete the following steps.
1. Attach the mounting brackets to both sides of the chassis. Insert the screws and tighten them with a screwdriver to secure the brackets.
2. Position the chassis in the stationary equipment rack. Allow 1-inch of clearance between units.
3. Have an assistant hold the unit in position, with the oval holes in the brackets aligned with the mounting holes in the rack posts, as you insert two rack screws and tighten
them with the appropriate screw driver.
2
Figure 3. Attaching Brackets to the Switch
Figure 4. Attaching Brackets to the Rack Post
617101561PF2-13A