AC Infinity CLOUDRAY T10 User Manual page 31

Whole house fan system
Hide thumbs Also See for CLOUDRAY T10:
Table of Contents

Advertisement

PROGRAMMING
TRANSITION HUMIDITY SETTING
In this setting, adjust the incremental rules in which
the fan speed ramps up or down for humidity triggers
in AUTO Mode. Press the up or down button to cycle
through 0% to 8% to set a differential increment.
Once setup, when the sensor humidity first meets
or exceeds the high humidity trigger, the speed will
start at one speed above the speed set in OFF Mode.
Then for every differential increment that the sensor
humidity is different from the set humidity, the speed
of the fan will ramp up by one additional speed level.
This continues until the fan reaches the speed set in
ON Mode.
For example, let's assume your high humidity trigger
is set at 67%, the speed set in OFF Mode is 2, and
the speed set in ON Mode is 7. If the differential
increment was set to 0%, then the fan would have
just triggered to run at speed 7 when the sensor
temperature meets or exceeds 67%. However, if
the differential increment was set to 5%. Then the
fan would start running at speed 3 when it meets
or exceeds 67%. Then at speed 4 when it meets
or exceed 72%. Then at speed 5 when it meets or
exceeds 77%. Then at speed 6 when it meets or
exceed 82%. Then from 87% or higher, it will run at
speed 7 which was the speed set in ON Mode.
31

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents