AUMA SQ 05.2 Operation Instructions Manual page 79

Part-turn actuators
Hide thumbs Also See for SQ 05.2:
Table of Contents

Advertisement

SQ 05.2
SQ 14.2 / SQR 05.2
AC 01.2 Intrusive Modbus RTU
Features and functions
Fieldbus interface with additional
output signals (option)
Voltage output
Redundancy (option)
FO cable connection (option)
Local controls
SQR 14.2 Control unit - electromechanical
Additional, binary output signals (only available in combination with additional input signals (option)
6 programmable output contacts:
-
5 potential-free NO contacts with one common, max. 250 V AC, 1 A (resistive load)
Default configuration: End position CLOSED, end position OPEN, selector switch REMOTE,
torque fault CLOSE, torque fault OPEN
-
1 potential-free change-over contact, max. 250 V AC, 5 A (resistive load)
Default configuration: Collective fault signal (torque fault, phase failure, motor protection tripped)
6 programmable output contacts:
-
5 potential-free change-over contacts with one common, max. 250 V AC, 1 A (resistive load)
-
1 potential-free change-over contact, max. 250 V AC, 5 A (resistive load)
6 programmable output contacts:
-
6 potential-free change-over contacts without one common, max. 250 V AC, 5 A (resistive load)
6 programmable output contacts:
-
4 mains failure proof potential-free NO contacts with one common, max. 250 V AC, 1 A (resistive
load), 1 potential-free NO contact, max. 250 V AC, 1 A (resistive load), 1 potential-free change-
over contact, max. 250 V AC, 5 A (resistive load)
6 programmable output contacts:
-
4 mains failure proof potential-free NO contacts, max. 250 V AC, 5 A (resistive load), 2 potential-
free change-over contacts, max. 250 V AC, 5 A (resistive load),
All binary output signals must be supplied with the same potential.
Analogue output signal for position feedback
-
Galvanically isolated position feedback 0/4
Standard:
Auxiliary voltage 24 V DC: max. 100 mA for supply of control inputs, galvanically isolated
from internal voltage supply.
Option:
Auxiliary voltage 115 V AC: max. 30 mA for supply of control inputs, galvanically isolated
from internal voltage supply
(Not possible in combination with PTC tripping device)
Redundant line topology with universal redundancy behaviour according to AUMA redundancy I or II
Redundant loop topology in combination with SIMA Master Station
Max. number of actuators with actuator controls per redundant loop: 247 units
Max. possible cable length between the actuators equipped with actuator controls without external
repeater: 1,200 m
Max. possible total length per redundant ring: approx. 290 km
Automatic commissioning of the redundant ring by means of the SIMA Master Station
Connector types: ST or SC connector
FO cables
-
Multi-mode: 62,5(50)/125 µm, range approx. 2.5 km (max. 2.0 dB/km)
-
Single-mode: 9/125 µm, range approx. 15 km (max. 0.4 dB/km)
Topologies: Line, star and redundant ring (with single-channel Modbus RTU interface)
Baud rate: up to 115.2 kbit/s
Optical budget:
-
Multi-mode: 13 dB
-
Single-mode: 17 dB
Wave length: 1,310 mm
FO coupler by EKS required at DCS, reference addresses: AUMA or www.eks-engel.com
Standard:
Selector switch: LOCAL - OFF - REMOTE (lockable in all three positions)
Push buttons OPEN, STOP, CLOSE, RESET
-
Local STOP
The actuator can be stopped via push button STOP of local controls if the selector
switch is in position REMOTE. (Not activated when leaving the factory.)
6 indication lights:
-
End position and running indication CLOSED (yellow), torque fault CLOSE (red),
motor protection tripped (red), torque fault OPEN (red), end position and running
indication OPEN (green), Bluetooth (blue)
Graphic LC display: illuminated
Option:
Special colours for the indication lights:
-
End position CLOSED (green), torque fault CLOSE (blue), torque fault OPEN
(yellow), motor protection tripped (violet), end position OPEN (red)
20 mA (load max. 500 Ω)
Technical data
79