Chapter 3 Specifications; General Specifications - Mitsubishi Electric NZ2MF2S1-32D User Manual

Cc-link ie field network basic remote i/o module
Hide thumbs Also See for NZ2MF2S1-32D:
Table of Contents

Advertisement

3
SPECIFICATIONS
This chapter describes the specifications of the I/O module.
3.1

General Specifications

Item
Operating ambient temperature
Storage ambient temperature
Operating ambient humidity
Storage ambient humidity
Vibration resistance
Shock resistance
Operating atmosphere
*1
Operating altitude
Installation location
*3
Overvoltage category
*4
Pollution degree
Equipment class
*1 Do not use or store the I/O module under pressure higher than the atmospheric pressure of altitude 0m. Doing so may cause
malfunction. When using the I/O module under pressure, please consult your local Mitsubishi representative.
*2 If the environment satisfies the operating ambient temperature, operating ambient humidity and other conditions, the module can be
used even outside the control panel.
*3 This indicates the section of the power supply to which the equipment is assumed to be connected between the public electrical power
distribution network and the machinery within premises.
Category  applies to equipment for which electrical power is supplied from fixed facilities. The surge voltage withstand level for up to
the rated voltage of 300V is 2500V.
*4 This index indicates the degree to which conductive material is generated in terms of the environment in which the equipment is used.
Pollution degree 2 is when only non-conductive pollution occurs. A temporary conductivity caused by condensing must be expected
occasionally.
To ensure that this product complies with the EMC Directive, refer to the following.
Page 129 EMC and Low Voltage Directives
3 SPECIFICATIONS
16
3.1 General Specifications
Specifications
0 to 55
-25 to 75
5 to 95%RH, non-condensing
Compliant with JIS
B 3502 and IEC
61131-2
Under intermittent
vibration
Under continuous
vibration
Compliant with JIS B 3502 and IEC 61131-2 (147m/, 3 times each in X, Y, and Z directions)
No corrosive gases, flammable gases, less conductive dust
0 to 2000m
*2
Inside a control panel
 or less
2 or less
Class 
Frequency
Constant
acceleration
5 to 8.4Hz
8.4 to 150Hz
9.8m/
5 to 8.4Hz
8.4 to 150Hz
4.9m/
Half amplitude
Sweep count
3.5mm
10 times each in X,
Y, and Z directions
1.75mm

Advertisement