• Automatic setting of the first to third octet of IP address is executed only once during the initial
communication with the master station after the I/O module is powered on. When the IP address of the I/O
module in the network parameter at the master station is changed while the data link between the I/O
module and master station is established, power off and on the I/O module as well after the parameter of
master station is reflected.
• The subnet mask for automatic setting of the first to third octet of IP address is 255.255.255.0 (fixed). If the
subnet mask needs to be set to the value other than 255.255.255.0, set the IP address and subnet mask
manually. ( Page 122 Setting IP Addresses and Subnet Masks)
• If the module is powered on while the IP address setting switch is 0, IP address is not set automatically.
Operation starts with the IP address and subnet mask set from the configuration tool of the master station.
( Page 122 Setting IP Addresses and Subnet Masks)
6 INSTALLATION AND WIRING
6.2 Setting Switch
6
71