Mitsubishi Electric NZ2MF2S1-32D User Manual page 112

Cc-link ie field network basic remote i/o module
Hide thumbs Also See for NZ2MF2S1-32D:
Table of Contents

Advertisement

■Action
Take either of the following two actions:
• Action 1: To suppress the back EMF, connect a diode parallel to the load where back EMF is generated in [3].
[3]
Sink output
+ Back electromotive force -
Load
• Action 2: Configure a sneak current path by connecting a diode across positive and negative of the external power supply.
When simultaneously taking an action for the case where load is briefly turned on when powering on the external power
supply, connect the diode in parallel with C1 and R1 as shown in the frame of dotted line.
Sink output
Y0
ON
Y1
OFF
COM-
CTL+
Source output
Y0
ON
Y1
OFF
COM+
CTL-
D1:
Reverse voltage VR (VRM)
Forward current IF (IFM)
*1 Approximately 10 times as large as the rated voltage in the specifications
Example: 24VDC  Approximately 200V
*2 Twice as much as the maximum load current (common) in the specifications or more
Example: 2A/1 common  4A or more
11 TROUBLESHOOTING
110
11.4 Examples of Troubles with the I/O Module
+ Back electromotive force - [3]
Load
[2]
Load
[1] Shut off
D1
C1 R1
Example 1
- Back electromotive force + [3]
Load
[2]
Load
[1] Shut off
D1
C1 R1
Example 1
*1
*2
Source output
- Back electromotive force +
Load

Advertisement

Table of Contents
loading

Table of Contents