Possible Forms Of Connections - WEG Drive Scan Manual

Low voltage devices
Hide thumbs Also See for Drive Scan:
Table of Contents

Advertisement

Table 5.18: Ethernet hardware accessory of the SSW900 compatible with the Modbus TCP protocol
Accessory
CMB-TCP-N
Parameter
Net ID
C8.3.4
760
C8.3.5
762
C8.3.6
761
C8.3.7
766
C8.3.9.1
771
C8.3.9.2
772
C8.3.9.3
759

5.6.3 POSSIBLE FORMS OF CONNECTIONS

Figure 5.9
illustrates the possible ways to connect the SSW900 to the Drive Scan.
WEG item
12966038
Table 5.19: Parameters related to the CMB-TCP-N
Description
IP address configuration
IP address
CIDR (subnet mask)
Gateway
Timeout mode
Timeout error action
Modbus TCP timeout
CONNECTING A DEVICE TO THE DRIVE SCAN
Modbus TCP
SSW900
clients
firmware
≥ V1.00
2
Values range
0 = Parameters
1 = DHCP
0.0.0.0 a 255.255.255.255
0 = Reserved
1 = 128.0.0.0
2 = 192.0.0.0
3 = 224.0.0.0
4 = 240.0.0.0
5 = 248.0.0.0
6 = 252.0.0.0
7 = 254.0.0.0
8 = 255.0.0.0
9 = 255.128.0.0
10 = 255.192.0.0
11 = 255.224.0.0
12 = 255.240.0.0
13 = 255.248.0.0
14 = 255.252.0.0
15 = 255.254.0.0
0.0.0.0 a 255.255.255.255
0 = Inactive
1 = F131 fault
2 = A131 alarm
0 = Only indicates
1 = Ramp stop
2 = General disable
3 = Go to LOC
4 = Go to REM
0 a 999,9s
Low Voltage Devices | 5-21
Parameters
Table 5.19
16 = 255.255.0.0
5
17 = 255.255.128.0
18 = 255.255.192.0
19 = 255.255.224.0
20 = 255.255.240.0
21 = 255.255.248.0
22 = 255.255.252.0
23 = 255.255.254.0
24 = 255.255.255.0
25 = 255.255.255.128
26 = 255.255.255.192
27 = 255.255.255.224
28 = 255.255.255.240
29 = 255.255.255.248
30 = 255.255.255.252
31 = 255.255.255.254