Possible Forms Of Connection - WEG Drive Scan Manual

Medium voltage devices
Hide thumbs Also See for Drive Scan:
Table of Contents

Advertisement

CONNECTING A DEVICE TO THE DRIVE SCAN
5
Figure 5.11: Configuring the Etor converter as Server in Gateway Master
After the configurations it's possible to establish a connection between the MVW-01, Etor and Drive Scan. For
that, it is necessary to connect one of the RS485 communication accessories (EBA, EBB or CSI2) to the drive.
Then, the RS485 accessory output signals must be connected to the Etor RS485 pins (GND, + and -).
So, you can connect the Etor to the Drive Scan using an Ethernet cable.
It's also necessary to supply the Etor with a 18V to 50VDC voltage range. The
Figure 5.23
illustrates all the
connections between MVW-01, Etor and Drive Scan.
Figure 5.12: Connections between MVW-01, Etor and Drive Scan
The ethernet interface communication parameters used to setup the Etor are analogous to those listed in
Table
5.2.
It's also important to observe the following setting:
Maximum number of simultaneous clients connected to the RS485 accessory.

5.2.3 POSSIBLE FORMS OF CONNECTION

Figure 5.13
illustrates the possible ways to connect the MVW-01 to the Drive Scan.
Medium Voltage Devices | 5-7

Advertisement

Table of Contents
loading

This manual is also suitable for:

Drive specialist

Table of Contents