WEG Drive Scan Manual page 23

Low voltage devices
Hide thumbs Also See for Drive Scan:
Table of Contents

Advertisement

CONNECTING A DEVICE TO THE DRIVE SCAN
The maximum number of clients connected simultaneously to the accessory;
The minimum Drive Scan version compatible the with the CFW11 firmware.
For additional information, see the document "Anybus-CC Communication Modules" of the CFW11, which can be
found in the download center at the website
Table 5.4: Ethernet hardware accessories of the CFW11 compatible with the Modbus TCP protocol
Accessory
MODBUSTCP-05
(1 or 2 ports)
ETHERNETIP-05
(1 or 2 ports)
PROFINETIO-05
5
Table 5.5: Parameters related to the MODBUSTCP-05, ETHERNETIP-05 and PROFINETIO-05 accessories
Parameter
P0723
P0724
P0725
P0840
P0841
P0842
P0843
P0844
P0846
P0847
P0848
Low Voltage Devices | 5-4
www.weg.net
WEG item
11550476 (1P)
14033951 (2P)
10933688 (1P)
12272760 (2P)
11550548
Description
Anybus identification
Anybus communication status
Anybus address
Anybus status
Ethernet baud rate
Modbus TCP timeout
IP address configuration
IP1 address
IP2 address
IP3 address
IP4 address
by searching for the keyword "anybus-cc".
Modbus TCP
CFW11
clients
Firmware
up to 4
≥ V6.00
up tp 2
Values range
0 = Inactive
10 = RS485
19 = EtherNet/IP
21 = Modbus TCP
23 = PROFINET IO
Other = Not compatible with drive scan
0 = Inactive
1 = Not supported
2 = Access error
3 = Offline
4 = Online
0 a 255
0 = Setup
1 = Init
2 = Wait Comm
3 = Idle
4 = Data Active
5 = Error
6 = Reserved
7 = Exception
8 = Access Error
0 = Auto 1 = 10 Mbps, half duplex
2 = 10 Mbps, full duplex
3 = 100 Mbps, half duplex
4 = 100 Mbps, full duplex
0 a 655 s
0 = Parameters
1 = DHCP
2 = DCP
3 = IPconfig
0 a 255
0 a 255
0 a 255
0 a 255
Parameters
Table 5.5

Advertisement

Table of Contents
loading

This manual is also suitable for:

Drive specialist