CONNECTING A DEVICE TO THE DRIVE SCAN
Parameter
P0311
P0312
P0313
P0314
5
P0316

5.5.2 ETHERNET

To connect to the WCD-ED300 via Ethernet GbE1 communication interface, using the Modbus TCP protocol, it is
necessary to install on the CFW500 one of the accessories listed in
Table 5.14: Ethernet hardware accessories of the CFW500 compatible with the Modbus TCP protocol
Accessory
CETH-IP
CEMB-TCP
Parameter
P0800
P0801
P0803
P0806
P0810
Low Voltage Devices | 5-16
Table 5.13: Parameters related to the RS-485 communication accessories
Description
Serial interface byte configuration
Serial protocol
Action for communication error
Serial watchdog
Serial interface status
WEG Item
12892814
12892815
Table 5.15: Parameters related to the CETH-IP and CEMB-TC accessories
Description
Ethernet module identification
Ethernet communication status
Ethernet baud rate
Modbus TCP watchdog
IP address configuration
Values range
0 = 8 bits, no parity, 1 stop bit
1 = 8 bits, even parity, 1 stop bit
2 = 8 bits, odd parity, 1 stop bit
3 = 8 bits, no parity, 2 stop bits
4 = 8 bits, even parity, 2 stop bits
5 = 8 bits, odd parity, 2 stop bits
2 = Modbus RTU
0 = Inactive
1 = Ramp stop
2 = General disable
3 = Go to local
4 = Go to local e mantém comandos e referência
5 = Fault cause
0,0 a 999,0 s
0 = Inactive
1 = Active
2 = Watchdog error
Table
5.14.
Modbus TCP
Firmware
clients
CFW500
2
≥ V2.00
4
Values range
0 = Not identified
1 = Modbus TCP
2 = Ethernet/IP
3 = PROFINET IO
0 = Setup
1 = Init
2 = Wait Comm
3 = Idle
4 = Data Active
5 = Error
6 = Reservado
7 = Exception
8 = Access Error
0 = Auto 1 = 10 Mbps, half duplex
2 = 10 Mbps, full duplex
3 = 100 Mbps, half duplex
4 = 100 Mbps, full duplex
0 a 65,5 s
0 = Parameters
1 = DHCP
Parameters
Table 5.15