Cfw100 Frequency Inverter; Possible Forms Of Connections - WEG Drive Scan Manual

Low voltage devices
Hide thumbs Also See for Drive Scan:
Table of Contents

Advertisement

CONNECTING A DEVICE TO THE DRIVE SCAN

5.3 CFW100 FREQUENCY INVERTER

5.3.1 RS-485
To connect the CFW100 to the WCD-ED300 via the RS-485 communication interface using the Modbus-RTU
protocol, it is necessary to install on the CFW100 the accessory listed in
firmware versions are v1.0 and above.
Refer to the CFW100 RS-485 Serial Communication guide, which can be obtained from the download center at
www.weg.net, for additional information.
It is important to note that there is no Ethernet communication support for the CFW100.
Table 5.6: RS-485 hardware accessory of the CFW100 compatible with the Modbus RTU protocol
Accessory
5
CRS485
Parameter
P0308
P0310
P0311
P0312
P0313
P0314
P0316

5.3.2 POSSIBLE FORMS OF CONNECTIONS

Figure 5.6
illustrates the possible ways to connect the CFW100 to the Drive Scan.
Low Voltage Devices | 5-8
WEG item
Parameters
11710626
Table 5.9
Table 5.7: Parameters related to the RS-485 communication accessories
Description
Serial address
Serial baud rate
Serial interface byte configuration
Serial protocol
Action for communication error
Serial watchdog
Serial interface status
Table
5.6. The supported CFW100
A signal pin (-)
B signal pin (+)
6
7
Values range
1 a 247
0 = 9600 bps
1 = 19200 bps
2 = 38400 bps
0 = 8 bits, no parity, 1 stop bit
1 = 8 bits, even parity, 1 stop bit
2 = 8 bits, odd parity, 1 stop bit
3 = 8 bits, no parity, 2 stop bits
4 = 8 bits, even parity, 2 stop bits
5 = 8 bits, odd parity, 2 stop bits
2 = Modbus RTU
0 = Inactive
1 = Ramp stop
2 = General disable
3 = Go to local
4 = Go to local and holds command and reference
5 = Fault cause
0,0 a 999,0 s
0 = Inactive
1 = Active
2 = Watchdog error
GND signal pin
8