National Instruments FieldPoint FP-1300 User Manual page 40

Hide thumbs Also See for FieldPoint FP-1300:
Table of Contents

Advertisement

Appendix C
Specifications
Isolation Voltage
Environmental
Safety
Electromagnetic Compatibility
Note
For full EMC compliance, you must operate this device with shielded cabling.
FP-1300 User Manual
For isolation voltage ratings, refer to the I/O module specifications and
labels.
FieldPoint modules are intended for indoor use only. For outdoor use, they
must be mounted inside a sealed enclosure.
Operating temperature .............................. –40 to 70 °C
Storage temperature .................................. –55 to 85 °C
Humidity ................................................... 10 to 90% RH, noncondensing
Maximum altitude..................................... 2,000 m
Pollution Degree ....................................... 2
The FP-1300 is designed to meet the requirements of the following
standards for safety and electrical equipment for measurement, control, and
laboratory use.
EN 61010-1, IEC 61010-1
UL 3121-1
CAN/CSA C22.2 No. 1010.1
For certifications under regulatory standards, including hazardous location
standards, refer to the product label or to
CE, C-Tick, and FCC Part 15 (Class A) Compliant
............................................. EN 55011 Class A @ 10 m
Emissions
............................................. EN 61326-1: 1998, Table 1
Immunity
ni.com
FCC Part 15A above 1 GHz
C-2
.
ni.com

Advertisement