LED Indicators
LED
POWER
Power is applied
to the FP-1300.
MODULE
The FP-1300 is
STATUS
operating
normally.
CAN STATUS
The CAN bus is
transmitting
messages.
Note
Refer to Appendix B, Troubleshooting, for more information about the LED
indicators.
© National Instruments Corporation
The FP-1300 has three LEDs that communicate information. Use
Table A-1 to interpret the FP-1300 LED indicators.
Table A-1. FP-1300 LED Indicators
Solid Green
Flashing Green
I/O data has
stopped because
the FP-1300 is
communicating
with the
Configuration
Utility.
Solid Red
The FP-1300 had
an unrecoverable
fault. Cycle the
power.
There is an error
on the CAN bus
and the CAN
communication
has stopped.
A-1
A
Flashing Red
The FP-1300 had
a recoverable
fault. Try using
the FP-1300
Configuration
Utility to resolve
the issue.
There is a
message
overflow on the
FP-1300 CAN
controller. In the
Configuration
Utility, select
Reset»Cycle
Power.