1.
Plug the Combicon-style connector into the CAN port.
N N ATIO O NAL
INSTRUMENTS
XTD
STD
ADDRESS
CAN
+
V
C_H
SH
C_L
Figure 2-16. CAN Port Terminals on the FP-1300
2.
Connect a twisted-pair cable to the CAN_H and CAN_L terminals.
The maximum recommended cable length between the FP-1300 and
the CAN network is 0.3 m (12 in.). CAN_H and CAN_L carry the data
on the CAN network.
3.
Connect a 10–30 VDC power supply to the V+ and V– terminals.
V+ and V– supply bus power to the CAN bus on the FP-1300.
4.
If you are using shielded cable, connect one end of the shield to the
Shield terminal. This connection is not required for all CAN networks.
Connecting a cable shield to the Shield terminal helps reduce noise.
5.
Connect the other end of the CAN cable to a connector on the CAN
network.
Chapter 2
Installing and Configuring Hardware and Software
FP-1300
CAN Network Interface
STD
USER
XTD DEF
-
V
V+
C_H
1
2
2-17
SH
C_L
V–
3
4
5
FP-1300 User Manual