Installation of the communication cards

4.6 UPS remote control functions

Connectivity cards
Connectivity cards allow the UPS to communicate in a variety of networking environments and with different types of
devices. The 5PX models have one available communication bay for the following connectivity cards:
Gigabit Network card (Network-M2) : provides a Gigabit Ethernet connection and enables secure UPS monitoring
over HTTPS web browser interface, SNMP v1/v3 protocol and email alarms. In addition, up to 3 Environmental
Monitoring Probes can be attached to obtain humidity, temperature, smoke alarm, and security information.
Industrial Gateway card (INDGW-M2) : Provides Modbus RTU and Modbus TCP communication support in addition
to the same secure UPS monitoring, management and sensor capability as the Gigabit Network card.  
Relay-MS card : provides isolated dry contact (Form-C) relay outputs for UPS status: Utility failure, Battery low, UPS
alarm/OK, or on Bypass.
INDRELAY-MS : The Industrial relay Card-MS (INDRELAY-MS) provides a simple way to remotely input UPS information
to an alarm system, PLC or a computer system via dry contacts. It offers five isolated dry contact outputs and one
isolated dry contact input.
614-40094-00
It is not necessary to shutdown the UPS before
installing a communication card.
1.
Remove the slot cover (9) secured by screws.
2.
Insert the communication card in the slot.
3.
Secure the card cover with the two screws to
connect the comm card to the ground.