Eaton 5PX Advanced User's Manual page 26

Hide thumbs Also See for 5PX:
Table of Contents

Advertisement

Programmable signal inputs
The 5PX incorporates several programmable signal inputs: one Remote Power Off (RPO) input terminal, one Remote On/
Off (ROO) input terminal, one RS-232 input (pin-4).
Signal inputs can be configured (see Settings > Comm settings > Signal Input) to have one of the following functions: 
Function
No
RPO
ROO
Building alarm
Shutdown commands
Warning: signal inputs have no function by default; please choose a function through the LCD (Settings > Com
settings > Input signals).
See below 2 examples of configuration with RPO terminal used as RPO function and ROO terminal use as ROO function:
Remote Power Off (RPO)
RPO is used to shutdown the UPS remotely when the contact is open. This feature can be used for shutting down the load
and the UPS by thermal relay, for example, in the event of room over temperature. When RPO is activated, the UPS turns
off the output and shuts down all power converters immediately (except for logic power). The UPS remains "ON" to alarm
the fault.
The RPO circuit is an IEC 60950 safety extra low voltage (SELV) circuit. This circuit must be separated from any hazardous
voltage circuits by reinforced insulation.
The RPO must not be connected to any utility connected circuits. Reinforced insulation to the utility is required. The
RPO switch must be a dedicated latching-type switch not tied into any other circuit. The RPO signal must remain
active for at least 250 ms for proper operation.
To ensure the UPS stops supplying power to the load during any mode of operation, the input power must be
disconnected from the UPS when the Remote Power Off function is activated.
RPO connections:
Remote On/Off (ROO)
Remote On/Off allows remote action of button to switch On/Off the UPS.
When contact changes from open to closed, the UPS is switched-on (or stays On).
When contact changes from closed to open, the UPS is switched-off (or stays Off).
614-40094-00
Description
No function. (Please choose a function if you want to use input signal.)
Remote Power off (RPO) is used to shutdown the UPS remotely.
Remote On/Off allows remote action of a button or other interface to switch On/
Off the UPS. (Cold start is prohibited while using the ROO function.)
Active input generates an alarm "building alarm".
Active input turns UPS output (or outlet groups) off after a user defined
shutdown delay but keeps on charging batteries according to a selected charging
scheme; inactive input does not abort shutdown countdown. Depending on the
"Restart" parameter (see Settings > Comm Settings > Shutdown commands) the
unit may startup automatically.
RPO
Connector type
Terminal rating
Comments
Terminal, 14 AWG Maximum
wires
60 V DC/30 V AC 20 mA max
26